CLEAR STOP

 

LECKAGESCHUTZ

MONTAGE- UND BETRIEBSANLEITUNG

WATER LEAK PROTECTION SYSTEM

OPERATING INSTRUCTIONS

SYSTEM OCHRONNY WYCIEKU WODY 

INSTRUKCJA MONTAŻU I EKSPLOATACJI

conel.de

CLEAR

WASSER-

AUFBEREITUNG

Summary of Contents for CLEAR STOP

Page 1: ...EAR STOP LECKAGESCHUTZ MONTAGE UND BETRIEBSANLEITUNG WATER LEAK PROTECTION SYSTEM OPERATING INSTRUCTIONS SYSTEM OCHRONNY WYCIEKU WODY INSTRUKCJA MONTA U I EKSPLOATACJI conel de CLEAR WASSER AUFBEREITU...

Page 2: ...SCHUTZES 13 6 BETRIEB 14 6 1 FUNKTIONSBESCHREIBUNG 14 6 2 INBETRIEBNAHME 14 6 3 BEDIENFELD 15 6 4 MEN FUNKTIONEN 16 6 5 EINSTELLUNG DER GRENZWERTE 17 6 6 AUTOMATISCHER BETRIEB 18 6 7 FFNEN SCHLIESSEN...

Page 3: ...3 7 1 REINIGUNG 27 7 2 GEW HRLEISTUNG UND WARTUNG 27 8 ST RUNG 28 9 ERSATZTEILE 29 10 TECHNISCHE DATEN 30 11 ZUBEH R 30 12 KUNDENDIENST 31...

Page 4: ...30 C geeignet Der Leckageschutz sch tzt vor den Auswirkungen von Wasserrohrbr chen und Leckagen Au erdem kann der Leckageschutz zur Begrenzung von au ergew hnlich hohem Wasserverbrauch eingesetzt wer...

Page 5: ...n Instandsetzung Installation und Instandhaltung darf nur durch vom Hersteller autorisiertes Personal erfolgen das in der Lage ist die in der Einbau und Betriebsanleitung genannten Anweisungen und die...

Page 6: ...Internationalen Einheitensystem SI Syst me International d Unit s werden folgende Einheiten und Begriffe verwendet Achtung Dieses Zeichen weist auf einen Punkt hin der f r einen zuverl ssigen Betrieb...

Page 7: ...fertig vormontierter Leckageschutz inkl 4 Befestigungsschrauben und Profilflanschdichtung Einbaudrehflansch mit Bajonettanschluss und Verschraubung Netzger t Montage und Betriebsanleitung Bitte pr fen...

Page 8: ...ole und Sicherheitshinweise F r hieraus resultierende Sch den haftet der Hersteller Lieferer nicht Das Risiko tr gt allein der Anwender Zur bestimmungsgem en Verwendung geh rt auch das Beachten der Be...

Page 9: ...htungen die nicht spritzwassergesch tzt sind und sich in der N he des Leckage schutzes befinden k nnen durch Wasser das bei der Montage oder bei unsachgem er Verwendung aus dem Leckageschutz austritt...

Page 10: ...Installation muss trocken und frostfrei sein Unbefugte Personen d rfen zu dem Raum keinen Zutritt haben Der Leckageschutz darf keinen starken St en ausgesetzt sein Der Leckageschutz wird in der Regel...

Page 11: ...lie en 5 4 EINBAUMASSE Montage des Leckageschutzes in horizontale oder vertikale Rohrleitungen m glich F r das Netzger t des Leckageschutzes ist oberhalb des Filters im Abstand von h chstens 1 5 m ein...

Page 12: ...he des Einbaudrehflanschsmuss vertikal stehen Der Einbaudrehflansch muss so montiert werden dass keine mechanischen Verspannungen auftreten Ansonsten kann es zu einer mechanischen Besch digung bis hin...

Page 13: ...nschs entfernen Die K pfe der vier Zylinderschrauben M6 100 durch die Bajonettbohrungen am Einbaudrehflansch stecken siehe Abb 4 I Den Leckageschutz im Uhrzeigersinn bis zum Anschlag drehen siehe Abb...

Page 14: ...serhahn hinter dem Leckage schutz voll aufdrehen Nach einer Sp lwassermenge von 5 Litern ist der Leckageschutz entl ftet Der Leckageschutz ist nun betriebsbereit Nach dem Einstecken des Netzger ts pr...

Page 15: ...e Funktionen Abb 6 Bedienfeld des Leckageschutzes Taste Funktion Zugang zum Hauptmen Bl ttern im Men nach oben Wert vergr ern Bl ttern im Men nach unten Wert verkleinern eine Men ebene zur ck ohne zu...

Page 16: ...hlie en siehe Kapitel 6 7 manuelles ffnen oder Schlie en des Absperrventils Sleepmodus siehe Kapitel 6 11 Sleepmodus 6 h starten Grenzwerte siehe Kapitel 6 5 maximale Entnahmemenge maximaler Volumenst...

Page 17: ...ten eingestellt werden Wenn bei den normalen Verbrauchsgewohnheiten regelm ig einer der Grenzwerte berschritten wird ohne dass eine Leckage vorliegt kann der entsprechende Grenzwert auf einen gr eren...

Page 18: ...errventil Das Absperrventil bleibt geschlossen Beispiel maximale Entnahmemenge maximaler Volumenstrom maximale Entnahmezeit Einfamilienhaus 2 Personen keine Drucksp ler 200 l 35 l min 30 min Einfamili...

Page 19: ...bsperrventil automatisch Das geschlossene Absperrventil und die jeweilige Abschaltursache werden auf dem Display angezeigt WICHTIG Bei vorhandener Warmwasserbereitung insbesondere bei gas oder elektri...

Page 20: ...nstellen Taste und anschlie end Taste 3x bet tigen Das Display zeigt Folgendes Taste OK bet tigen mit der Taste den gew nschten Urlaubsmodus ausw hlen und mit der Taste OK speichern Es stehen die folg...

Page 21: ...in der Stellung auf befinden Sleepmodus starten Taste und anschlie end Taste 1x bet tigen Das Display zeigt Folgendes Taste OK bet tigen Das Display zeigt Folgendes Nach Bet tigen der Taste OK wird de...

Page 22: ...um Beispiel bei Stromausfall durch Geb udebrand Dies ist besonders wichtig wenn L schwasser ben tigt wird Netzger t ausstecken Vordere Verkleidung abnehmen siehe Abb 7 Hintere Verkleidung 1 etwas nach...

Page 23: ...er laufenden Wasserentnahme statt 6 14 MEN STRUKTUR Abb 8 Men struktur IIQHQ 6FKOLH HQ HWULHEVGDWHQ QIR 0D QWQDKPHPHQJH 0D 9ROXPHQVWURP 0D QWQDKPH HLW HFNDJHVFKXW VFKOLH HQ HOHXFKWXQJ RQWUDVW HUNVHLQV...

Page 24: ...6 17 WARTUNG REPARATUR Bei Nichtbeachtung kann es durch unkontrolliertes Austreten von Wasser zu Wassersch den im Haus kommen Die in Kapitel 5 EINBAU und Kapitel 7 INSTANDHALTUNG genannten Anweisungen...

Page 25: ...r bei Betriebsdruck undicht wird oder bersten kann Durch austretendes Wasser k nnen gr ere Sachsch den im Haus entstehen Au erdem k nnen Personen die sich in der N he des Leckageschut zes aufhalten du...

Page 26: ...werts maximale Entnahmemenge das Absperrventil des Leckage schutzes geschlossen wurde siehe Kapitel 6 6 AUTOMATISCHER BE TRIEB Leckageschutz geschlossen im Wechsel mit Volumenstrom berschritten im We...

Page 27: ...stungszeit hi naus Es ist anzustreben dass die regelm igen Wartungsarbeiten und die Versorgung mit Verschlei material durch das Fachhandwerk oder den Werkskundendienst erfolgen Sleepmodus ein Zeit 6 h...

Page 28: ...halters nach 30 s noch nicht erkannt St rmeldung zur cksetzen Taste OK dr cken oder Netzger t aus der Steckdose ziehen und nach ca 5 s wieder einstecken Falls St rung erneut auftritt Netzger t ausstec...

Page 29: ...29 9 ERSATZTEILE Abb 9 Ersatzteile CLEAR STOP Ersatzteilliste CLEAR STOP Pos Benennung St ck Best Nr 1 Netzger t 1 2210506 2 Elektronische Steuerung 1 2990330 3 Turbine Sicherungsring 1 2140117 1 2 3...

Page 30: ...ss 4 m h Druckverlust bei Nenndurchfluss 0 5 bar Wasser und Umgebungstemperatur max 30 C Abmessungen Breite x H he x Tiefe 203 x 141 x 143 mm einstellbare Grenzwerte max Entnahmemenge 0 1 bis 3 m max...

Page 31: ...CLEAR von CONEL f r Ausk nfte gerne zur Verf gung Deutschland T 49 0 7195 692 0 Frankreich T 33 0 3 88 65 93 94 Wir empfehlen Ihnen dringend einen Wartungsvertrag abzuschlie en damit alle Wasseraufbe...

Page 32: ...l rung ihre G ltigkeit Produktbezeichnung 5 6723 HFNDJHVFKXW Auf dieses Produkt angewDndte Richtlinien 5ichtlinie 2014 3 E8 OHNWURPDJQHWLVFKH 9HUWU JOLFKNHLW 09 Harmonisierte NormHQ 1 XQG 1 OHNWURPDJQ...

Page 33: ...33 Notizen Notes Notatki...

Page 34: ...N SYSTEM 45 6 OPERATION 46 6 1 FUNCTION DESCRIPTION 46 6 2 COMMISSIONING 46 6 3 CONTROL PANEL 47 6 4 MENU FUNCTIONS 48 6 5 SETTING THE LIMIT VALUES 49 6 6 AUTOMATIC OPERATION 50 6 7 OPENING CLOSING OF...

Page 35: ...35 7 1 CLEANING 59 7 2 WARRANTY AND SERVICE 59 8 FAULT 60 9 SPARE PARTS 61 10 TECHNICAL DATA 62 11 ACCESSORIES 62 12 CUSTOMER SERVICE 63...

Page 36: ...he water leak protection system protects against the effects of water pipe breakages and leaks Moreo ver the water leak protection system can be used to protect against exceptionallyhigh water consump...

Page 37: ...tion repair Installation and maintenance must only be performedby personnel who have been authorised by the man ufacturer to do so i e who are able to fulfil the instructions referred to in the instal...

Page 38: ...and maintained so that they are always legible The following units and terms which do not form part ofthe SI Syst me International d Unit s system are used Attention This symbol refers to a point whic...

Page 39: ...a profiled flange gasket Built in rotary flange with bayonet connection and compression fitting Power supply unit Installation and operating instructions Immediatelyafterunpackingpleasechecktheshipme...

Page 40: ...ting damage All risks are borne solely by the user Intended use includes observance of the operating instructions The manufacturer supplier must be consulted before using the leak protection system ou...

Page 41: ...LLATIONS Electrical devices installations that are not splash proof and are located in the vicinity of the leak protec tion system may be damaged by water that escapes during installation or in the ev...

Page 42: ...The installationroommustbedryandfreefromfrost Itmustnotbepossibleforunauthorisedpersons to access the room The water leak protection system must not be subject to severe impacts In general the leak p...

Page 43: ...NSTALLATION DIMENSIONS The leak protection system can be installed in horizontal or vertical pipes A splash proof socket complying with the legal regulations for wet areas is re quired for the power s...

Page 44: ...ce of the built in rotary flange must be vertical The built in rotary flange must be fitted so that it is free from mechanical stress or strain Otherwise mechanical damage to the pipe or the built in...

Page 45: ...heads of the four M6 100 hexagon socket head screws through the bayonet holes on the built in rotary flange see fig 4 I Screw the water leak protection system fully home in a clockwise direction see f...

Page 46: ...ap downstream of the leak pro tection system After a flushing water quantity of 5 litre the leak protection system is bled The leak protection system is now ready for operation After the power supply...

Page 47: ...e following functions Fig 6 Control panel of the leak protection system Key Function Access to the main menu Scroll up in the menu Increase value Scroll down in the menu Reduce value Jump a menu level...

Page 48: ...anual opening or closing of the shut off valve Sleep mode see chapter 6 11 Start 6 h sleep mode Limit values see chapter 6 5 Max water volume drawn Max volume flow rate Max drawing time Holiday mode s...

Page 49: ...p tion habits a limit value is regularly exceeded without a leak being present the corresponding limit value can be reset to a larger value Hauptmen Grenzwerte Grenzwerte Max Entn menge Limit value Lo...

Page 50: ...me drawn Maximum volume flow rate Maximum drawing time Single family dwelling 2 persons no pressure flushing valves 200 litre 35 litre minute 30 minutes Single family dwelling 4 persons no pressure fl...

Page 51: ...shut off valve closes automatically The closed shut off valve and the relevant switching off cause are shown on the display NOTE If a hot water heating system is fitted especially in the case of gas...

Page 52: ...ss key and then key 3x The display shows the following Press the OK key select the desired holiday mode with key and confirm with the OK key The following holiday modes are available No holiday mode H...

Page 53: ...e shut off valve must also be in the Open position Start sleep mode Press key and then key 1x The display shows the following Press the OK key The display shows the following After pressing the OK key...

Page 54: ...e loss of power as a re sult of a house fire This is particularly important when extinguishing water is needed Unplug the power supply unit Remove forward cover panel see fig 7 Press rear cover panel...

Page 55: ...ace while water is being drawn 6 14 MENU STRUCTURE Fig 8 Menu structure 2SHQLQJ ORVLQJ 2SHUDWLQJ GDWD QIR 0D YROXPH GUDZQ 0D YROXPH IORZ UDWH 0D GUDZLQJ WLPH DFNOLJKW RQWUDVW DFWRU VHWWLQJ DWHU TXDQWL...

Page 56: ...SERVICE REPAIR If this is ignored the result may be uncontrolled egress of water resulting in water damage to the building home Therefore the instructions given in chapter 5 INSTALLATION and chapter...

Page 57: ...ion system may be so badly me chanically damaged that it leaks at the operating pressure or can even burst Escaping water can cause serious property damage in the home Moreover persons in the vicinity...

Page 58: ...rotection sys tem has been closed due to exceed ing of theMaximumvolumedrawn limit value see chapter 6 6 AUTOMATIC OPERA TION Leckageschutz geschlossen alternating with Volumenstrom berschritten alter...

Page 59: ...sirable that the regular maintenance work and the supply of wear parts is performed by a technical service provider or the factory customer service team Sleepmodus ein Zeit 6 h The message appears if...

Page 60: ...ot detected after 30 s Reset fault message Press OK key or Pull the power supply unit out of the socket and plug back in after about 5 s If fault occurs again Unplug the power supply unit Manually tur...

Page 61: ...SPARE PARTS Fig 9 Spare parts CLEAR STOP List of spare parts CLEAR STOP Item Designation Piece s Order no 1 Power supply unit 1 2210506 2 Electronic control unit 1 2990330 3 Turbine circlip 1 2140117...

Page 62: ...h Pressure drop at nominal flow 0 5 bar Water and ambient temperature max 30 C Dimensions width x height x depth 203 x 141 x 143 mm Adjustable limit value max volume drawn 0 1 to 3 m max volume flow r...

Page 63: ...CONEL will be happy to provide you with any information you may require Germany T 49 0 7195 692 0 France T 33 0 3 88 65 93 94 We strongly recommend that you take out a service contract so that all wa...

Page 64: ...l rung ihre G ltigkeit Produktbezeichnung 5 6723 HFNDJHVFKXW Auf dieses Produkt angewDndte Richtlinien 5ichtlinie 2014 3 E8 OHNWURPDJQHWLVFKH 9HUWU JOLFKNHLW 09 Harmonisierte NormHQ 1 XQG 1 OHNWURPDJQ...

Page 65: ...65 Notizen Notes Notatki...

Page 66: ...WEGO 76 5 6 MONTA ZABEZPIECZENIA PRZED NIESZCZELNO CI 77 6 EKSPLOATACJA 78 6 1 OPIS DZIA ANIA 78 6 2 ROZRUCH 78 6 3 POLE OBS UGI 79 6 4 FUNKCJE MENU 80 6 5 USTAWIENIE WARTO CI GRANICZNYCH 81 6 6 PRACA...

Page 67: ...67 7 1 CZYSZCZENIE 91 7 2 R KOJMIA I KONSERWACJA 91 8 B D 92 9 CZ CI ZAMIENNE 93 10 DANE TECHNICZNE 94 11 AKCESORIA 94 12 SERWIS 95...

Page 68: ...omie maks 30 C Zabezpieczenie przed nieszczelno ci chroni przed skutkami p kni rur wodnych i nieszczelno ciami Mo e r wnie s u y do ograniczenia niestandardowo wysokiego zu ycia wody Wszystkie funkcje...

Page 69: ...praw Prace w ramach monta u i utrzymania ruchu mog przeprowadza wy cznie pracownicy upowa nieni przez producenta kt rzy s w stanie wype ni zalecenia wskazane w instrukcji monta u i eksploatacji oraz p...

Page 70: ...w pe ni czytelne Odmiennie od mi dzynarodowego uk adu jednostek miar SI Syst me International d Unit s stosowane s nast puj ce jednostki Uwaga Ten znak wskazuje punkt kt rego trzeba bezwzgl dnie prze...

Page 71: ...DOSTAWY Zmontowane wst pnie zabezpieczenie przed nieszczelno ci wraz z 4 rubami mocuj cymi i profilowan uszczelk ko nierzow Ko nierz obrotowy ze z czem bagnetowym i po czeniem skr canym Zasilacz Inst...

Page 72: ...Za szkody wynikaj ce z tego tytu u producent dostawca nie odpowiada Ryzyko ponosi wy cznie u ytkownik Do zakresu stosowania zgodnego z przeznaczeniem nale y r wnie przestrzeganie zapis w w instrukcji...

Page 73: ...TRYCZNE Przyrz dy urz dzenia elektryczne nie zabezpieczone przed bryzgami wody a znajduj ce si w pobli u za bezpieczenia przed nieszczelno ci mog zosta uszkodzone przez wod wyciekaj c z zabezpieczenia...

Page 74: ...racza 30 C Przestrze instalacyjna musi by sucha i zabezpieczona przed mrozem Osoby postronne nie mog mie dost pu do pomieszczenia Zabezpieczenie przed nieszczelno ci nie mo e by nara one na silne uder...

Page 75: ...mkn 5 4 WYMIARY MONTA OWE Mo liwy monta zabezpieczenia przed nieszczelno ci w rurach poziomych lub pionowych Dla zasilacza zabezpieczenia przed nieszczelno ci powy ej filtra w odleg o ci maksymalnie 1...

Page 76: ...si by ustawiona pionowo Ko nierz obrotowy zamontowa w taki spos b aby nie wyst powa y napr enia mechaniczne W przeciwnym razie mo e doj do uszkodzenia mechanicznego a nawet do p kni cia ruroci gu lub...

Page 77: ...monta ow ko nierza by czterech rub walcowych M6 100 przetkn przez otwory bagnetowe ko nierza patrz rys 4 I Przekr ci zabezpieczenie przed nieszczelno ci w prawo do oporu patrz rys 4 II Mocno dokr ci c...

Page 78: ...ie czeniem przed nieszczelno ci Po przep ukaniu oko o 5 l wody urz dzenie jest odpowietrzone Zabezpieczenie przed nieszczelno ci jest teraz gotowe do pracy Po w o eniu zasilacza do gniazdka sterownik...

Page 79: ...ce funkcje Rys 6 Pole obs ugi zabezpieczenia przed nieszczelno ci Przycisk Funkcja Dost p do menu g wnego Przewijanie menu w g r Zwi ksz warto Przewijanie menu w d Zmniejsz warto Jeden poziom menu ws...

Page 80: ...e zaworu odcinaj cego Tryb u pienia patrz rozdzia 6 11 Uruchom tryb u pienia 6 h Warto ci graniczne patrz rozdzia 6 5 maksymalna ilo wody maksymalny strumie obj to ci maksymalny czas poboru Tryb urlop...

Page 81: ...ykizu ycia Je eli przynormalnym zu yciu re gularnie przekraczane s warto ci graniczne bez wyst powania nieszczelno ci mo na ustawi wy sz warto graniczn Hauptmen Grenzwerte Grenzwerte Max Entn menge wa...

Page 82: ...przed nieszczelno ci zamyka natychmiast zaw r odcinaj cy Zaw r odcinaj cy pozo staje zamkni ty Przyk ad maksymalny ilo wody maksymalny strumie obj to ci maksymalny czas poboru dom jednorodzinny 2 oso...

Page 83: ...IA Poprzekroczeniujednejz ustawionychwarto cigranicznych zaw rodcinaj cyzamykasi automatycznie Zamkni ty zaw r odcinaj cy i dana przyczyna wy czenia widoczne s na ekranie WA NE Je eli dost pny jest uk...

Page 84: ...acisn przycisk a nast pnie 3 przycisk Widok na ekranie Nacisn przycisk OK przyciskiem wybra odpowiedni tryb urlopowy i zapisa przyciskiem OK Dost pne s nast puj ce tryby urlopowe Brak trybu urlopowego...

Page 85: ...y w tym celu ustawiony w pozycji otw Uruchomienie trybu u pienia Nacisn przycisk a nast pnie 1 przycisk Widok na ekranie Nacisn przycisk OK Widok na ekranie Po naci ni ciu przycisku OK uruchamia si tr...

Page 86: ...zasilania np przy awarii pr du wskutek po aru budynku Ma to szczeg lne znaczenie wtedy gdy wymagana jest woda ga nicza Od czy zasilacz Zdj przedni obudow patrz rys 7 Wcisn tyln obudow 1 nieco do ty u...

Page 87: ...Rys 8 Struktura menu 2SHQLQJ ORVLQJ 2SHUDWLQJ GDWD QIR 0D YROXPH GUDZQ 0D YROXPH IORZ UDWH 0D GUDZLQJ WLPH DFNOLJKW RQWUDVW DFWRU VHWWLQJ DWHU TXDQWLW WRWDO LVWRU HYLFH QR 6RIWZDUH YHUVLRQ 0HDVXUHG YD...

Page 88: ...pi niekontrolowany wyciek wody co w konse kwencji mo e spowodowa znaczne szkody w budynku Bezwzgl dnie przestrzega instrukcji wyszczeg l nionych w rozdzia 5 MONTA oraz rozdzia 7 UTRZYMANIE RUCHU 6 18...

Page 89: ...pod ci nieniem roboczym b dzie nieszczelne lub p knie Wyciekaj ca woda mo e skutkowa powa ne szkody w budynku Ponadto osoby przebywaj ce w pobli u zabezpie czenia mog dozna uraz w spowodowanych przez...

Page 90: ...lna ilo wody za w r odcinaj cy zabezpieczenia przed nieszczelno ci zosta za mkni ty patrz rozdzia 6 6 PRACA W TRYBIE AU TOMATYCZNYM Leckageschutz geschlossen na zmian z Volumenstrom berschritten na zm...

Page 91: ...warancyjnym Nale y d y do tego aby za regularne prace konserwacyjne i zaopatrzenie w materia y zu ywaj ce si odpowiadali specjali ci lub serwis zak adowy Sleepmodus ein Zeit 6 h Komunikatpojawia si po...

Page 92: ...nie jest zostaje jeszcze rozpoznana po 30 s Kasowanie komunikatu o b dzie Nacisn przycisk OK lub Wyci gn zasilacz z gniazdka i w o y po nownie po ok 5 s Je eli b d pojawi si ponownie Od czy zasilacz P...

Page 93: ...CI ZAMIENNE Rys 9 Cz ci zamienne CLEAR STOP Lista cz ci zamiennych CLEAR STOP Poz Nazwa Szt Nr kat 1 Zasilacz 1 2210506 2 Sterownik elektroniczny 1 2990330 3 Turbina pier cie zabezpieczaj cy 1 214011...

Page 94: ...raty ci nienia przy przep ywie znamionowym 0 5 bar Temperatura wody i otoczenia maks 30 C Wymiary szeroko wysoko g boko 203 141 143 mm Nastawne warto ci graniczne Maks ilo wody od 0 1 do 3 m Maks stru...

Page 95: ...ji Niemcy T 49 0 7195 692 0 Francja T 33 0 3 88 65 93 94 Pilnie zaleca si zawarcie umowy serwisowej na wykonywanie regularnych fachowych przegl d w aby urz dzenia uzdatniaj ce wod mog y by regularnie...

Page 96: ...l rung ihre G ltigkeit Produktbezeichnung 5 6723 HFNDJHVFKXW Auf dieses Produkt angewDndte Richtlinien 5ichtlinie 2014 3 E8 OHNWURPDJQHWLVFKH 9HUWU JOLFKNHLW 09 Harmonisierte NormHQ 1 XQG 1 OHNWURPDJQ...

Page 97: ...97 Notizen Notes Notatki...

Page 98: ...98 Notizen Notes Notatki...

Page 99: ...99 Notizen Notes Notatki...

Page 100: ...CONEL GmbH Margot Kalinke Str 9 80939 M nchen S mtliche Bild Ma und Ausf hrungsangaben entsprechen dem Tag der Drucklegung nderungen die dem technischen Fortschritt und der Weiterentwicklung dienen b...