Operation Manual
Track Supply 6 kW
80 / 125 A at 400 / 480 V
BAL9100-0124c-EN
www.conductix.com
Page 10 of 44
6.1.3
Electrical input data – specifications for 480 V versions
•
Input nominal supply voltage
480 V / 60 Hz, 3-phase symmetric, neutral grounded
•
Supply voltage tolerance
-10% to + 10%, with proportional cont. power de-rating for input
voltages other than nominal value
•
Efficiency at rated load
94%
•
Power factor (cos
ϕ
)
0.78
•
Supply current
10 A at rated power / voltage
•
Input connector
Supplied HAN-6HSB in Han-16B connector with PG 21 or M25
cable gland. Maximum outside cable diameter is 18 mm. Use
flexible cable 6 mm
2
.
•
Input leakage current
19 mA rms in standby. Occasional 200 mA peak pulses for 250 µsec
at rated load. Ground leakage equipment must be rated accordingly if
used.
•
Internal fuses
12A JKS, HSJ, DFJ Fast Class J
•
Harmonic current (rated load)
5th -4.3dB, 7th -9.1dB, 11th -18.7dB, 13th -19.7dB (on fundamental)
6.2
Physical data
•
Noise levels
During operation 65 dBA at 1m distance in front
•
Air volume moved
50 m³ / hour (air recirculation)
•
Fan
3 axial fans