Operation Manual
Track Supply 6 kW
80 / 125 A at 400 / 480 V
BAL9100-0124c-EN
www.conductix.com
Page 13 of 44
6.5
Interfaces
Track connection
(X1)
Pin Function
Remarks
1
Track cable 1
20 (80 A) - 35 (125A) mm² lug
HF Litz cable *
2
Track cable 2
* = cable shoes with M8 hole, Soldered only!
Connection to AC mains supply
(X2); Harting HAN-6HSB / Han-16B Housing
Pin Function
Rating
Remarks
1
L1
12 / 10 A
I depending on load and input voltage
2
L2
12 / 10 A
I depending on load and input voltage
3
L3
12 / 10 A
I depending on load and input voltage
PE
PE
Control and synchronization
(X3); Harting HAN-10E
Pin Function
Rating
Remarks
1
Start +
24 V
24 V present = start
2
Start -
0 V
3
/Reset +
24 V
0 V = reset
4
/Reset -
0 V
5
ErrorRelay
1 A
24 V
Normally closed, open on error
6
Error Relay
7
24 V supply
100 mA
Not for external distribution!
8
0 V
9
Synchronization
+15 V
10
Synchronization
For more details on X1, X2 and X3 and their connection refer to chapter 10.5 “Electrical connection”.
6.6
General features
•
Input line chokes
will drop 4% from the mains voltage at rated load
•
EMC filtering
Built in line filter included
•
Start-up inrush current
< 10 A
•
Mains to output isolation
High frequency isolation transformer
•
Internal cooling fans
3 axial fans