71
Mounting and installation work
5.7.7 Performance data / Fuses "F3" Heating voltage supply
230V/1~/50...60 Hz
200V/3~/50...60 Hz
230V/3~/50...60 Hz
380V/3~/50...60 Hz
400V/3~/50...60 Hz
415V/3~/50...60 Hz
Max. steam capacity in kg/h
P
N
max.
in kW
I
N
max. in A Cable cross section A
L
min. in mm
2
Fuses "F3"
in
A, quick acting (gR)
Max. steam capacity in kg/h
P
N
max.
in kW
I
N
max. in A Cable cross section A
L
min. in mm
2
Fuses "F3"
in
A, quick acting (gR)
Max. steam capacity in kg/h
P
N
max.
in kW
I
N
max. in A Cable cross section A
L
min. in mm
2
Fuses "F3"
in
A, quick acting (gR)
Max. steam capacity in kg/h
P
N
max.
in kW
I
N
max. in A Cable cross section A
L
min. in mm
2
Fuses "F3"
in
A, quick acting (gR)
Max. steam capacity in kg/h
P
N
max.
in kW
I
N
max. in A Cable cross section A
L
min. in mm
2
Fuses "F3"
in
A, quick acting (gR)
Max. steam capacity in kg/h
P
N
max.
in kW
I
N
max. in A Cable cross section A
L
min. in mm
2
Fuses "F3"
in
A, quick acting (gR)
S
RS 5
8.0
4.0 16.5 4.0
20
––
––
––
––
––
5.0
3.8
9.4
1.5
16
4.6
3.4
5.2
1.5
10
5.0
3.8
5.5
1.5
10
5.4
4.1
6.0
1.5
10
RS 8
8.0
6.5 26.0 6.0
32
––
––
––
––
––
8.0
6.0 15.0 2.5
20
7.3
5.4
8.3
1.5
10
8.0
6.0
8.7
1.5
10
8.7
6.5
9.0
1.5
10
RS 10
9.8
8.0 32.0 10.0 40
––
––
––
––
––
9.8
7.4 18.5 6.0
32
9.0
6.7 10.2 1.5
16 10.0 7.5 11.0 1.5
16 10.7 8.0 11.5 1.5
16
M
RS 16
––
––
––
––
–– 14.9 11.2 32.2 10.0 40 16.0 12.0 30.1 10.0 40 14.5 10.9 16.6 2.5
20 16.0 12.0 17.4 2.5
20 17.3 13.0 18.1 2.5
20
RS 20
––
––
––
––
–– 18.1 13.6 39.2 16.0 63 19.7 14.8 37.1 16.0 63 17.9 13.4 20.4 6.0
25 20.0 14.9 21.5 6.0
25 21.4 16.0 22.3 4.0
25
RS 24
––
––
––
––
–– 22.3 16.7 48.3 16.0 63 24.0 18.0 45.1 16.0 63 21.8 16.3 24.8 6.0
32 24.0 18.1 26.2 6.0
32 26.0 19.5 27.2 6.0
32
RS 30
––
––
––
––
–– 30.0 22.5 65.0 25.0 80 29.5 22.1 55.6 25.0 80 26.9 20.1 30.6 10.0 40 30.0 22.3 32.3 10.0 40 32.0 24.0 33.5 10.0 40
RS 40
––
––
––
––
––
––
––
––
––
––
––
––
––
––
–– 36.1 27.1 41.1 16.0 63 40.0 30.0 43.3 16.0 63 43.1 32.3 45.0 16.0 63
2*M
RS 40
––
––
––
––
–– 2*18.1 2*13.6 2*39.2 2*16.0 2*63 2*19.7 2*14.8 2*37.1 2*16.0 2*63 ––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
RS 50
A
+
B
––
––
––
––
––
18.1
+
30.0
13.6
+
22.5
39.2
+
65.0
16.0
+
25.0
63
+
80
19.7
+
29.5
14.8
+
22.1
37.1
+
55.6
16.0
+
25.0
63
+
80
17.9
+
26.9
13.4
+
20.1
20.4
+
30.6
6.0
+
10.0
25
+
40
20.0
+
30.0
14.9
+
22.3
21.5
+
32.3
6.0
+
10.0
25
+
40
21.4
+
32.0
16.0
+
24.0
22.3
+
33.5
4.0
+
10.0
25
+
40
L
RS 50
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
–– 50.0 37.2 53.7 25.0 80 53.4 40.0 57.7 16.0 63
2*M
RS 60
––
––
––
––
–– 2*30.0 2*30.0 2*65.0 2*25.0 2*80 2*29.5 2*22.1 2*55.6 2*25.0 2*80 2*26.9 2*20.1 2*30.6 2*10.0 2*40 2*30.0 2*22.3 2*32.3 2*10.0 2*40 2*32.0 2*24.0 2*33.5 2*10.0 2*40
L
RS 60
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
–– 60.0 44.6 64.4 25.0 80 64.0 48.0 69.3 25.0 80
2*M
RS 80
––
––
––
––
––
––
––
––
––
––
––
––
––
––
–– 2*36.1 2*27.1 2*41.1 2*16.0 2*63 2*40.0 2*30.0 2*43.3 2*16.0 2*63 2*43.1 2*32.3 2*45.0 2*16.0 2*63
L
RS 80
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
–– 80.0 60.0 86.6 35.0 125 86.2 64.6 93.2 35.0 125
3*M
RS 100
M
+
E
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
2*30.0
+
40.0
2*22.3
+
30.0
2*32.3
+
43.3
2*10.0
+
16.0
2*40
+
63
2*32.0
+
43.1
2*24.0
+
32.3
2*33.5
+
45.0
2*10.0
+
16.0
2*40
+
63
RS 120
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
–– 3*40.0 3*30.0 3*43.3 3*16.0 3*63 3*43.1 3*32.3 3*45.0 3*16.0 3*63
4*M
RS 140
M
+
E
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
2*30.0
+
2*40.0
2*22.3
+
2*30.0
2*32.3
+
2*43.3
2*10.0
+
2*16.0
2*40
+
2*63
2*32.0
+
2*43.1
2*24.0
+
2*32.3
2*33.5
+
2*45.0
2*10.0
+
2*16.0
2*40
+
2*63
RS 160
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
–– 4*40.0 4*30.0 4*43.3 4*16.0 4*63 4*43.1 4*32.3 4*45.0 4*16.0 4*63
440V/3~/50...60 Hz
460V/3~/50...60 Hz
480V/3~/50...60 Hz
500V/3~/50...60 Hz
600V/3~/50...60 Hz
Max. steam capacity in kg/h
P
N
max.
in kW
I
N
max. in A Cable cross section A
L
min. in mm
2
Fuses "F3"
in
A, quick acting (gR)
Max. steam capacity in kg/h
P
N
max.
in kW
I
N
max. in A Cable cross section A
L
min. in mm
2
Fuses "F3"
in
A, quick acting (gR)
Max. steam capacity in kg/h
P
N
max.
in kW
I
N
max. in A Cable cross section A
L
min. in mm
2
Fuses "F3"
in
A, quick acting (gR)
Max. steam capacity in kg/h
P
N
max.
in kW
I
N
max. in A Cable cross section A
L
min. in mm
2
Fuses "F3"
in
A, quick acting (gR)
Max. steam capacity in kg/h
P
N
max.
in kW
I
N
max. in A Cable cross section A
L
min. in mm
2
Fuses "F3"
in
A, quick acting (gR)
S
RS 5
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
RS 8
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
RS 10
10.8 8.1 10.6 1.5
16 11.8 8.8 11.1 1.5
16 12.8 9.6 11.5 1.5
16 13.9 10.4 12.0 1.5
16 10.3 7.7
7.4
1.5
16
M
RS 16
15.3 11.5 15.1 2.5
20 16.7 12.6 15.8 2.5
20 18.2 13.7 16.4 2.5
20 19.8 14.8 17.1 2.5
20 14.2 10.7 10.3 1.5
16
RS 20
17.2 12.9 16.9 2.5
20 18.8 14.1 17.7 4.0
25 20.5 15.4 18.5 4.0
25 22.2 16.7 19.2 4.0
25 21.3 16.0 15.4 2.5
20
RS 24
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
RS 30
24.0 18.0 23.6 6.0
32 26.2 19.7 24.7 6.0
32 28.6 21.4 25.8 6.0
32 31.0 23.3 26.9 6.0
32 32.0 24.0 23.1 6.0
32
RS 40
36.0 27.0 35.4 16.0 63 39.4 29.5 37.1 16.0 63 42.9 32.1 38.7 16.0 63 46.5 34.9 40.3 16.0 63 42.7 32.0 30.8 10.0 40
2*M
RS 40
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
RS 50
A
+
B
17.2
+
24.0
12.9
+
18.0
16.9
+
23.6
2.5
+
6.0
20
+
32
18.8
+
26.2
14.1
+
19.7
17.7
+
24.7
4.0
+
6.0
25
+
32
20.5
+
28.6
15.4
+
21.4
18.5
+
25.8
4.0
+
6.0
25
+
32
22.2
+
31.0
16.7
+
23.3
19.2
+
26.9
4.0
+
6.0
25
+
32
21.3
+
32.0
16.0
+
24.0
15.4
+
23.1
2.5
+
6.0
20
+
32
L
RS 50
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
2*M
RS 60
2*24.0 2*18.0 2*23.6 2*6.0 2*32 2*18.8 2*19.7 2*24.7 2*6.0 2*32 2*20.5 2*21.4 2*25.8 2*6.0 2*32 2*22.2 2*23.3 2*26.9 2*6.0 2*32 2*21.3 2*24.0 2*23.1 2*6.0 2*32
L
RS 60
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
2*M
RS 80
2*36.0 2*27.0 2*35.4 2*16.0 2*63 2*39.4 2*29.5 2*37.1 2*16.0 2*63 2*42.9 2*32.1 2*38.7 2*16.0 2*63 2*46.5 2*34.9 2*40.3 2*16.0 2*63 2*42.7 2*32.0 2*30.8 2*10.0 2*40
L
RS 80
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
3*M
RS 100
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
RS 120
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
4*M
RS 140
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
RS 160
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
––
A
= Module A,
B
= Module B,
M
= Main unit,
E
= Extension unit
Summary of Contents for RS series
Page 76: ...76 Appendix 6 2 EC Declaration of conformity...
Page 77: ...Notes...
Page 78: ...Notes...
Page 79: ......