![Condair RS series Installation Manual Download Page 20](http://html1.mh-extra.com/html/condair/rs-series/rs-series_installation-manual_2651779020.webp)
20
Product Overview
3.4.2.2 OptiSorp steam distribution system
The
OptiSorp
steam distribution system is used in ventilation ducts with a short humidification distance
(for the calculation of the humidification distance refer to
chapter 5.4.2
). When ordering an
OptiSorp
system the duct dimension must be specified. Please consult the data in the following table:
System 1
System 2
System 3
System 4
Number of
steam connector
1
2
3
4
Max. steam capacity
45 (30) kg/h
90 (60) kg/h
135 (90) kg/h
180 (120) kg/h
Duct width (B)
450...2700mm
Duct height (H)
450...1650 mm
450...2200 mm
800...3200 mm
800...3200 mm
* For duct widths <600 mm the value in brackets apply
Note: further information on the OptiSorp steam distribution system can be found in the separate manual
supplied with the OptiSorp steam distribution system.
H
B
H
B
H
B
H
B
Summary of Contents for RS series