Modbus Installation
Variable
Name
Description
Addr.
Type
Format
Range
Unit
R/W
Details
Set2Cyl2
Writes the
desired space
setpoint for
control channel
2 for cylinder 2
41010
Holding
Register
Integer
30-95
%
Write
Use only with NHTC-
150 and NHTC-200
models when sending
RH value to RHDem2
with dual channel
control enabled and
cylinders are in
independent operation
mode
DisableCyl1
Remotely
disable steam
production for
cylinder 1
40262
Holding
Register
Integer
0 or
255
-
Write
0 = Normal operation
255 = Disabled
DisableCyl2
Remotely
disable steam
production for
cylinder 2
41262
Holding
Register
Integer
0 or
255
-
Write
Used only for NHTC-
150 and NHTC-200
models. Both cylinder
1 and 2 must be
disabled to completely
disable humidifier.
0 = Normal operation
255 = Disabled
NetSensor
Switches
between hard
wired or
network control
signal
40226
Holding
Register
Integer
0 or 1
-
Write
1= Network sensor or
demand
0 = Wired sensor or
wired demand
Ch1DemCyl1
Displays
channel 1
demand for
cylinder 1
30348
Input
Register
Integer
0 - 100
%
Read
Displays channel 1
demand as a
percentage of cylinder
capacity for cylinder 1
Ch1DemCyl2
Displays
channel 1
demand for
cylinder 2
31348
Input
Register
Integer
0 - 100
%
Read
Displays channel 1
demand / output as a
percentage of cylinder
capacity for cylinder 2
(NHTC-150 and NHTC-
200 models only)
Ch2DemCyl1
Displays
channel 2
demand for
cylinder 1
30349
Input
Register
Integer
0 - 100
%
Read
Displays channel 2
demand as a
percentage of cylinder
capacity for cylinder 1
Ch2DemCyl2
Displays
channel 2
demand for
cylinder 2
31349
Input
Register
Integer
0 - 100
%
Read
Displays channel 2
demand / output as a
percentage of cylinder
capacity for cylinder 2
(NHTC-150 and NHTC-
200 models only)
Fault Warning
Reads fault
status
30301
Input
Register
Integer
0 or
255
-
Read
0 = No Fault
255 = Fault Warning
Service
Warning
Reads service
warning status
30300
Input
Register
Integer
0 or
255
-
Read
0 = No Service
Warning
255 = Service Warning
Unit Status
Reads unit
status
30312
Input
Register
Integer
0 or
255
-
Read
0 = Idle / Standby
255 = Active /
Humidifying
Cyl1OpTime
Reads operating
time for cylinder
1
30213
Input
Register
Integer
0 -
65535
5
min
Read
Reads operating time
for cylinder 1. Each
number is equivalent
to 5 minutes of
operation.
Time in hours = (Value
x 5)/60
Summary of Contents for Modbus RTU
Page 9: ...Modbus Installation 6 Figure 3 EL NH EL Modbus Wiring Diagram ...
Page 10: ...7 Modbus Installation Figure 4 TC Modbus Wiring Diagram ...
Page 11: ...Modbus Installation 8 Figure 5 MES2 and RH2 Modbus Wiring Diagram ...
Page 12: ...9 Modbus Installation Figure 6 NHRS Modbus Wiring Diagram ...
Page 43: ...Modbus Installation 40 The following points may be mapped for control ...
Page 44: ...41 Modbus Installation Table 8 MES2 and RH2 Humidifier Modbus Parameters ...
Page 52: ...49 Modbus Installation Troubleshooting Table 10 General Troubleshooting ...
Page 59: ...Modbus Installation 56 Figure 13 Low voltage terminal strip on NHRS Humidifier ...