Modbus Installation |
10
Addressing and Communications
Once the humidifier has been wired to the network, control variables must be mapped to allow
for control of the humidifier. The specific variables and communications requirements for each
humidifier are described in the following sections.
EL Electrode Steam Humidifiers
After wiring connections have been completed, the humidifier needs to be setup to operate and
communicate either through the Modbus or BACnet interface.
Modbus Communication Set-up
The default Modbus address for the EL is 10. If multiple units were included on an order, the
addresses of individual units may vary. To view or change the Modbus address:
1
Press the
Menu
icon on the lower left corner of the screen, to access the menu.
2
When prompted for a password, enter 0335 using the number pad. Press the
Check Mark
icon to confirm.
3
Select the
Configuration
menu.
4
Select the
Comms.
menu.
5
Using the navigation buttons on the top right of the screen, scroll down to the
Modbus
Parameters
.
Note: By default, Modbus is disabled. To enable Modbus, select
Modbus
under
Modbus
Parameters
. Select
ON
and confirm the selection by pressing the
Check Mark
button.
6
Select the
Modbus Address
setting. Using the
Up
and
Down
arrows, select a value between
1 and 247 inclusive as desired and press the
Check Mark
button
to confirm the selection. It
is recommended to leave the parity and baud rate settings to their factory defaults (Even
and 9600 respectively) unless communication problems occur.
7
Press
Back
repeatedly until you return to the home screen.
This procedure is summarized below:
Main Menu > 0335 > Configuration > Comms. Menu > Modbus Parameters >
Addr: 10 (1 – 247 acceptable)
Parity: Even (None, Even, Odd)
Baud Rate: 9600 (9600, 19200, 38400, 115200)
Summary of Contents for Modbus RTU
Page 9: ...Modbus Installation 6 Figure 3 EL NH EL Modbus Wiring Diagram ...
Page 10: ...7 Modbus Installation Figure 4 TC Modbus Wiring Diagram ...
Page 11: ...Modbus Installation 8 Figure 5 MES2 and RH2 Modbus Wiring Diagram ...
Page 12: ...9 Modbus Installation Figure 6 NHRS Modbus Wiring Diagram ...
Page 43: ...Modbus Installation 40 The following points may be mapped for control ...
Page 44: ...41 Modbus Installation Table 8 MES2 and RH2 Humidifier Modbus Parameters ...
Page 52: ...49 Modbus Installation Troubleshooting Table 10 General Troubleshooting ...
Page 59: ...Modbus Installation 56 Figure 13 Low voltage terminal strip on NHRS Humidifier ...