Parameter
Name
Description
Modbus
Addr.
Type
Format
Range
Unit
W/R
Details
System
Demand A
System Demand A
30006
Input
Register
Integer
0-100
%
READ
Demand Mode:
Summation of
Channel A1 and
Channel A2
RH Mode:
PID calculation
Safety Loop A
External safety
loop unit A
30007
Input
Register
Integer
0 OR 1
-
READ
0 = Open
1 = Closed
Blower Pack A
Blower ready unit
A
30008
Input
Register
Integer
0 OR 1
-
READ
0 = Open
1 = Closed
FanActivate A
External fan unit
A
30009
Input
Register
Integer
0 OR 1
-
READ
0 = Open
1 = Closed
Operating
Hours A
Operating hours
unit A
30010
Input
Register
Float CD
AB
0-5000
Hrs
FLOAT CD AB
Displays the total
time cylinder A has
been running since
last reset
Enable Input
B
Enable contact
unit B
30012
Input
Register
Integer
0 OR 1
-
READ
0 = Off
1 = On
Channel B1
Input signal
channel 1 unit B
30014
Input
Register
Integer
0-100
%
READ
Displays channel 1
demand/sensed RH
as a percentage of
cylinder capacity for
cylinder B (EL-150
and EL-200 models
only)
Channel B2
Limiter signal
channel 2 unit B
30015
Input
Register
Integer
0-100
%
READ
Displays channel 2
demand/sensed RH
as a percentage of
cylinder capacity for
cylinder B (EL-150
and EL-200 models
only)
System
Demand B
System Demand B
30016
Input
Register
Integer
0-100
%
READ
Demand Mode:
Summation of
Channel B1 and
Channel B2
RH Mode:
PID calculation
Safety Loop B
External safety
loop unit B
30017
Input
Register
Integer
0 OR 1
-
READ
0 = Open
1 = Closed
Blower Pack B
Blower ready unit
B
30018
Input
Register
Integer
0 OR 1
-
READ
0 = Open
1 = Closed
FanActivate B
External fan unit
B
30019
Input
Register
Integer
0 OR 1
-
READ
0 = Open
1 = Closed
Operating
Hours B
Operating hours
unit B
30020
Input
Register
Float CD
AB
0-5000
Hrs
FLOAT CD AB
Displays the total
time cylinder B has
been running since
last reset
Summary of Contents for Modbus RTU
Page 9: ...Modbus Installation 6 Figure 3 EL NH EL Modbus Wiring Diagram ...
Page 10: ...7 Modbus Installation Figure 4 TC Modbus Wiring Diagram ...
Page 11: ...Modbus Installation 8 Figure 5 MES2 and RH2 Modbus Wiring Diagram ...
Page 12: ...9 Modbus Installation Figure 6 NHRS Modbus Wiring Diagram ...
Page 43: ...Modbus Installation 40 The following points may be mapped for control ...
Page 44: ...41 Modbus Installation Table 8 MES2 and RH2 Humidifier Modbus Parameters ...
Page 52: ...49 Modbus Installation Troubleshooting Table 10 General Troubleshooting ...
Page 59: ...Modbus Installation 56 Figure 13 Low voltage terminal strip on NHRS Humidifier ...