Modbus Installation |
20
Parameter
Name
Description
Modbus
Addr.
Type
Format
Range Unit
R/W
Details
Humidifier_
Status_A
Reads the
status of the
unit for cylinder
A
30003
Input
Register
Integer
0 - 9
-
Read
0 = Humidifying
1 = Idle
2 = Idle Drain
3 = Keepwarm
4 = Filling
5 = Draining
6 = Disabled
7 = Safety Loop
8 = Warning
9 = Fault
Humidifier_
Status_B
Reads the
status of the
unit for cylinder
A
30026
Input
Register
Integer
0 - 9
-
Read
0 = Humidifying
1 = Idle
2 = Idle Drain
3 = Keepwarm
4 = Filling
5 = Draining
6 = Disabled
7 = Safety Loop
8 = Warning
9 = Fault
System_
Demand_A
Reads the
demand for
cylinder A
30006
Input
Register
Integer
0 – 100
%
Read
Demand Mode:
Summation of Input_A1 and
Input_A2
RH Mode:
PID calculation
System_
Demand_B
Reads the
demand for
cylinder A
30016
Input
Register
Integer
0 – 100
%
Read
Demand Mode:
Summation of Input_B1 and
Input_B2
RH Mode:
PID calculation
Safety_Loo
p_A
Reads the
status of the
safety loop for
cylinder A
30007
Input
Register
Integer
0 or 1
-
Read
0 = Open
1 = Closed
Safety_Loo
p_B
Reads the
status of the
safety loop for
cylinder B
30017
Input
Register
Integer
0 or 1
-
Read
0 = Open
1 = Closed
Run_Time_
A
Reads
operating time
for cylinder A
30010
Input
Register
Integer
0 -
5000
Hrs
Read
Displays the total time cylinder
A has been running since last
reset
Run_Time_
B
Reads
operating time
for cylinder B
30020
Input
Register
Integer
0 -
5000
Hrs
Read
Displays the total time cylinder
B has been running since last
reset
Weighted_
Hours_A
Reads the
weighted time
for cylinder A
30011
Input
Register
Integer
0 -
5000
Hrs
Read
An equated run time based on
Run_Time_A x
System_Demand_A
Weighted_
Hours_B
Reads the
weighted time
for cylinder B
30021
Input
Register
Integer
0 -
5000
Hrs
Read
An equated run time based on
Run_Time_A x
System_Demand_A
Summary of Contents for Modbus RTU
Page 9: ...Modbus Installation 6 Figure 3 EL NH EL Modbus Wiring Diagram ...
Page 10: ...7 Modbus Installation Figure 4 TC Modbus Wiring Diagram ...
Page 11: ...Modbus Installation 8 Figure 5 MES2 and RH2 Modbus Wiring Diagram ...
Page 12: ...9 Modbus Installation Figure 6 NHRS Modbus Wiring Diagram ...
Page 43: ...Modbus Installation 40 The following points may be mapped for control ...
Page 44: ...41 Modbus Installation Table 8 MES2 and RH2 Humidifier Modbus Parameters ...
Page 52: ...49 Modbus Installation Troubleshooting Table 10 General Troubleshooting ...
Page 59: ...Modbus Installation 56 Figure 13 Low voltage terminal strip on NHRS Humidifier ...