C
HANGING
H
IGH
T
EMPERATURE
D
EVIATION
UGH017/0500
Series 1 Portable Chillers, PLC Control
O
PERATION
4-11
Decide how many degrees above the setpoint temperature you
want the chiller to deviate before an alarm occurs.
To set the high temperature deviation:
Press the Setup arrow.
Continue to press the arrow to scroll through the Setup
screens. Stop when you get to the Deviate High screen.
The current high temperature deviation number displays
along with the - and +. The number flashes on the screen.
1
STATUS SETUP RUN ALM
press arrow
Press the - or + arrows to set the high
deviation to the appropriate number. Each press of the (-)
arrow decreases the high deviation by one unit; each press
of the (+) arrow increases the high deviation by one unit.
Stop when you reach the desired temperature deviation.
The allowable range is 3 to 20 units.
2
Press the Scroll arrows to scroll to the
the next Setup screen, or press the Escape/Previous
Screen button to return to the main screen.
High Temp Dev
18
Press arrows
High Temp Dev
2
0
number flashes
3