Rev.01 03-27-17
Page 33 of 67
Compu-Aire
8.1
Setpoints
The controller is shipped with default selections for all necessary settings. In some cases,
adjustments can be made to meet the application requirements. Use
Up
and
Down
arrow
buttons to navigate between settings for different sensor.
Default Settings:
•
Temperature: 72°F
Alarm hi/lo:
85 / 55
•
Humidity: 50%
65 / 35
•
Discharge temp: 55°F
•
Water in Econ: 50°F
8.1.1
Changing Setpoints
Press menu and navigate to setpoint. The cursor is shown on the upper left of the screen. Move the
cursor to the setpoint by pressing the enter key once. Use the up/down arrow keys to alter the setting.
Press enter to save the value. In order to navigate to next menu, move the blinking cursor to the upper
left and press the up/down arrow keys.
Note that only applicable setpoints are shown in the menu.
Figure 13 temperature setpoint
Figure 14 Discharge setpoint
Next menu
Previous menu