Rev.01 03-27-17
Page 32 of 67
Compu-Aire
8.0
SETUP MENU
“SETUP MENU” has three (3) levels of
passwords to control the access for accessing end user,
technician, and setting reserved for factory setup. A password must be supplied to gain access
to any setting. Level1 and level2 passwords are not enabled by default.
Note: Your system 2500 series controller is already programmed, configured, and tested for
your application. The system can be turned ON by using the ON/OFF through the graphical
interface or via through the quick menu. The operating mode (Active System, System OFF, or
Standby) is indicated under System Status screen. Entering a password
No password is required to view system status, active alarm, or turning the unit ON/OFF. System
is automatically locked out after 5 minutes of inactivity and returned to the main screen. A new
password must be entered to regain access to the setting. Once a password is entered, it times
out in five (5) minutes if no screen and button activity are detected. A higher level of password
also grants access to lower level access. If a factory password (level3) is enter, the screen will
return the main menu.
Figure 11 password prompt
Password
Level
Accessibility
0
1
Setpoint Menu
1
2
Technician Menu
1798
3
Factory Setup (Consult factory for more information)
Figure 12 default passwords
Note:
Entering a service menu requires a password. Default password is listed in
Table 5
.
Password is entered by using the up/down arrow. Each digit is input followed an enter button to move
to next digit.