Service Manual -
DVC 09/12/18/24 SF Series
45
51
8.2.
10
High temperature protection of IPM module or compressor top diagnosis and solution
(P2)
Error Code
P2
Malfunction conditions
If the sampling voltage is not 5V, the LED will display the failure.
Possible
causes
●
Installation
error
●
Power supply problems
●
System leakage or block
age
●
PCB faulty
Troubleshooting:
For
18k and 24k
Yes
No
Check if the Fastening screws
on the PCB and IPM radiator
are fixed tightly.
For other models,
Check if the air flow system
of indoor and outdoor units
are obstructed?
Clear up the air inlet and outlet or the heat
exchanger of indoor and outdoor units.
Yes
No
Yes
Yes
Turn off the power supply and turn
it on 10 minutes later.
Check if the temperature
of compressor
t
op
i
s more than
194°F?
No
Check if the refrigerant
system
is normal?
Repair the refrigerant
system .
Replace the outdoor control PCB.
Yes
Check if all the connection, especially
the connection of OLP (Over Load
Protector) sensor is good.
Correct the connection.
No
Measure the resistance
between the two ports of
the OLP. Is it zero?
Yes
Replace the OLP.
No
Replace the outdoor control PCB.
Yes
No
Tighten the screws and apply
silicon grease.
Replace the outdoor control PCB.
Summary of Contents for A-DVC09SF-0
Page 8: ...Service Manual DVC 09 12 18 24 SF Series 8 6 For B DVC09SF 0 For B DVC12SF 0 For B DVC18SF 1 ...
Page 9: ...Service Manual DVC 09 12 18 24 SF Series 9 7 For B DVC24SF 1 ...
Page 13: ...Service Manual DVC 09 12 18 24 SF Series 13 For A DVC24SF 1 ...
Page 14: ...Service Manual DVC 09 12 18 24 SF Series 14 4 Refrigerant Cycle Diagram ...
Page 42: ...Service Manual DVC 09 12 18 24 SF Series 42 47 P W N U ...
Page 43: ...Service Manual DVC 09 12 18 24 SF Series 43 48 N V N W ...
Page 55: ...Service Manual DVC 09 12 18 24 SF Series 55 This page intentionally left blank ...