8.2.1
1
Inverter compressor drive error diagnosis and solution
(P4)
Error Code
P4
Malfunction conditions
An abnormal inverter compressor drive is detected by a special
detection circuit, including communication signal detection,
voltage detection, compressor rotation speed signal detection
and so on.
Possible
causes
●
Wiring
error
●
IPM malfunction
●
Outdoor fan ass
embl
y faulty
●
Compressor malfunction
●
Outdoor PCB faulty
Troubleshooting:
Check if the wiring between main
PCB and compressor connected
well?
Correct the connection or
replace the wires and
connectors.
No
Is
the IPM installed correctly
?
Correct the installation,
tighten the screws and
apply silicon grease.
No
IPM continuity check.
Are
the IPM
terminal resistance values uniform
?
Yes
Replace the IPM board or replace
the main PCB if the IPM board and
main PCB are integrated together.
No
Check if the outdoor fan runs
properly or the outdoor unit
ventilation is good.
Yes
No
Please refer to the solution of
【
Fan
Speed Has Been Out Of Control
】
malfunction
Yes
Are
the compressor resistance
values uniform?
No
Replace the compressor.
Yes
Replace the outdoor main PCB.
Check the reactor or
Inductance .Is it normal?
No
Replace the reactor
or Induct
or
Yes
Yes
Summary of Contents for A-DVC09SF-0
Page 8: ...Service Manual DVC 09 12 18 24 SF Series 8 6 For B DVC09SF 0 For B DVC12SF 0 For B DVC18SF 1 ...
Page 9: ...Service Manual DVC 09 12 18 24 SF Series 9 7 For B DVC24SF 1 ...
Page 13: ...Service Manual DVC 09 12 18 24 SF Series 13 For A DVC24SF 1 ...
Page 14: ...Service Manual DVC 09 12 18 24 SF Series 14 4 Refrigerant Cycle Diagram ...
Page 42: ...Service Manual DVC 09 12 18 24 SF Series 42 47 P W N U ...
Page 43: ...Service Manual DVC 09 12 18 24 SF Series 43 48 N V N W ...
Page 55: ...Service Manual DVC 09 12 18 24 SF Series 55 This page intentionally left blank ...