IE-SNC-T03(4)10+T5410-06 

Info mode 

If in doubt of setting of installed device, verification of its address is enabled even without 

using computer. Power should be connected. Devices with RS232 interface have address always set 
to one. 

Unscrew device cover and shortly press button next to connection terminals (jumper should 

be  opened).  Actual  adjusted  address  of  the  device  is  displayed  on  LCD  display  at  decimal  base, 
for HWg-Poseidon’s  communication  protocol  there  is  shown  number  corresponding  with  ASCII 
address code. Next press of button exits info mode and actual measured values are displayed.  
 
Note:  No  measurement  and  communication  is  possible  during  info  mode.  If  device  stays  in info 
mode for longer than 15 s, device automatically returns to measuring cycle. 

Setting of pressure correction for altitude 

For device T5410 only! If there is necessary to read value of atmospheric pressure corrected 

with  respect  to  altitude,  it  is  possible  to  set  corresponding  pressure  offset  for  this  altitude.  It  is 
possible to do it with Users software. This value is then automatically added to measured pressure 
value. The resultant value of pressure with added correction for altitude must be between 300 hPa 
and 1350 hPa (from 4.351 PSI to 19.580 PSI). Outside this range device sends value of Error 2! 

Description of communication protocols 

Detailed  description  of  each  communication  protocols  including  examples  of 

communication  is  available  in  individual  document  “

Description  of  communication  protocols  of 

Txxxx series”

 which is free to download at  

www.cometsystem.com

. 

 
Note:  After switching  ON the power of the  device  it can last  up to  2 s before the  device  starts to 
communicate and measure! 

Modbus RTU 

Control units communicate on master-slave principle in half-duplex operation. Only master 

can  send  request  and  only  addressed  device  responds.  During  sending  of  request  no  other  slave 
station should respond. During communication, data transfer proceeds in binary format. Each Byte 
is sent as eight bit data word in format: 1 start bit, data word 8 bit (LSB first), 2 stop bits

1

, without 

parity. Device supports communication speed from 110Bd to 115200Bd. 

Sent request  and response have syntax: ADDRESS OF DEVICE  – FUNCTION – Modbus 

CRC 

Supported functions 

03 (0x03)

: Reading of 16-bit registers (Read Holding Registers) 

04 (0x04)

: Reading of 16-bit input gates (Read Input Registers) 

16 (0x10)

: Setting of more 16-bit registers (Write Multiple Registers) 

Jumper and button 

Jumper  and  button  are  located  next  to  connection  terminals.  If  communication  protocol  Modbus 
is selected the function of jumper and button is as follows: 

 

Jumper  opened  –  device  memory  is  protected  from  writing,  from  device  side  it  is  only 
enabled  to  read  measured  value,  writing  to  memory  is  disabled  (no  change  of  device 
address, communication speed and LCD setting is enabled). 

 

Jumper closed – writing to device memory is enabled by means of User’s software. 

 

1

 

Device sends two stop bits, for receive one stop bit is enough. 

Summary of Contents for T0310

Page 1: ...nd improvement of their products Manufacturer reserves the right to make technical changes to the device without previous notice Misprints reserved Manufacturer is not responsible for damages caused b...

Page 2: ...ware TSensor for setting of all device parameters recommended It is free to download at www cometsystem com It supports make the adjustment of the device too This procedure is described at file Calibr...

Page 3: ...nection to RS232 interface For devices with RS485 output there is recommended to use shielded twisted copper cable maximal length 1200m The cable must be located at indoor rooms Nominal cable impedanc...

Page 4: ...4 IE SNC T03 4 10 T5410 06 Dimensions T0410 T5410 Transmitter with RS485 Dimensions T0310L T0410L T5410L Connection see Appendix B...

Page 5: ...IE SNC T03 4 10 T5410 06 5 Typical application wiring connection of terminals T0310 power from communication port T0310 power from external voltage source T0410 T5410 RS485...

Page 6: ...tocols including examples of communication is available in individual document Description of communication protocols of Txxxx series which is free to download at www cometsystem com Note After switch...

Page 7: ...R Serial number of device Lo 0x1036 4150 BCD BIN16 R Version of Firmware Hi 0x3001 12289 BCD BIN16 R Version of Firmware Lo 0x3002 12290 BCD BIN16 R Addition for device T5410 with atmospheric pressure...

Page 8: ...pressed for longer than six seconds causes restoring of manufacturer setting of communication protocol i e sets Modbus RTU communication protocol device address sets to 01h and communication speed to...

Page 9: ...it of allowed full scale range There is a reading Err1 on LCD display Value read from the device is 999 9 for pressure reading there is 999 9 hPa correct value This state occurs if measured temperatur...

Page 10: ...ameters Ambient temperature RTD sensor Pt1000 3850ppm Measuring range 30 to 80 C Resolution of display 0 1 C Accuracy 0 4 C Atmospheric pressure T5410 only Unit hPa mBar PSI mmHg inHg inH2O oz in2 kPa...

Page 11: ...ions other than specified in technical parameters Devices are not designed for locations with chemically aggressive environment Temperature sensor must not be exposed to direct contact with water or o...

Page 12: ...the corresponding pins of CANON connector for more information see the operation manual for ELO E214 The ELO E06D converter is an optional accessory for connection of transmitter with RS485 interface...

Reviews: