A.6. 

LASER POINTER 

During commissioning, activation of the laser pointer makes it possible to check that the reflector has been positioned 
correctly in relation to the E / R. 
If the  zone  indicated  by the laser  beam is more than 5 cm away from the reflector, adjust the position  of the E / R, 
using the corresponding screws to bring the point indicated by the beam closer to the reflector. 
To activate the laser pointer: press the button and hold for more than a second, then release. 
To deactivate the laser pointer: press the button again. If the button is not pressed, it will deactivate automatically after 
a delay of 20 minutes. 

A.7. 

AUTOMATIC CALIBRATION 

Automatic calibration consists of defining and storing the parameters inside the detector, based on: 

  The distance between the E / R and the reflector, 

  The position of the reflector in relation to the E / R. 

Automatic  calibration  starts  automatically  when  the  laser  pointer  is 

deactivated

  after  the  button  is  pressed;  the 

automatic calibration sequence is as follows: 

During  automatic  calibration  the  barrier  may  trigger  the  alarm  for  the  conventional  zone  to  which  it  is 
connected if it is powered from that zone. 

Indicator light 

Step description 

Flashing green 

Automatic calibration in progress 

Steady green 

Automatic calibration performed correctly 

Flashing orange 

Automatic calibration error (1) 

1.  In this case, start a new automatic calibration process by pressing the button; take care not to block the infrared 

beam. 

Note: 

If the orange light flashes when you start the automatic calibration process (when you press the button to 

deactivate the laser pointer), make sure the detector and reflector are not exposed to direct sunlight. 

Note: 

If the orange light flashes after a succession of green pulses, carry out E / R alignment again so that the point 

indicated by the laser beam is on the reflector. 
 

A.8. 

ALIGNMENT CHECK 

This check allows you to make sure there are no parasitic reflections which could compromise detector operation. 
The  detector  automatically  enters  alignment  check  mode  after  an  automatic  calibration  procedure  has  been  carried 
out successfully. In this case: 
1.  The indicator light flashes red, 
2.  Completely mask the surface of the reflector with a non-reflective object (packaging cardboard, for example) for at 

least 10 seconds, 

3.  While the masking is in place, the indicator light may assume one of the two following statuses: 

Indicator light 

Meaning 

Steady green 

Acceptable reflection level 

Flashing red 

Excessive parasitic reflection level (see note) 

4.  Exit alignment check mode by pressing the button or by restarting the control panel. 

Note: 

While the reflector is masked, it is wise to search for reflective objects along the route of the infrared beam and 

cover them in order to obtain the green indication. After this search, there are two alternative solutions: 

  Cover the reflective objects permanently, 

  Move the detector. 

Caution: 

 

Take  all  necessary  precautions  to  avoid  activating  the  evacuation  process  or  ordering  activations 
accidentally. 

 

This check does not in any way replace actual standardised tests, but can be used during  servicing test 
procedures. 

 
Note: 

If the indicator light does not turn red to indicate an alarm within 40 seconds, disconnect the detector from the 

power supply for 2 minutes and repeat the commissioning procedures. 

Summary of Contents for 48BFC000

Page 1: ...1 OPTICAL BEAM LINEAR SMOKE DETECTOR WITH REFLECTOR 3 30 M 48BFC000 Please read this manual before using the equipment and keep it safe for future reference...

Page 2: ...with national installation regulations Make sure both the detector and reflector can be accessed for commissioning and maintenance procedures A 2 2 Rules for the installation site The E R and the ref...

Page 3: ...Securing the reflector 6 Deactivating the laser pointer press button Caution Leave a free area of at least 30 cm around each element installed on the wall A 2 4 Flush mounted base The flush mounted b...

Page 4: ...ified the point indicated by the laser beam The reflector is secured in 2 steps Step 1 securing the safety reflector support Use screws with a maximum diameter of 4 mm to secure the safety reflector s...

Page 5: ...2 x 0 5 mm2 cables are recommended for COM COM and TL TL respectively The K terminal is connected by means of a wire from a 2 x 0 5 mm2 cable COMMISSIONING A 4 MAIN STEPS Commissioning takes place by...

Page 6: ...you press the button to deactivate the laser pointer make sure the detector and reflector are not exposed to direct sunlight Note If the orange light flashes after a succession of green pulses carry o...

Page 7: ...ection rating E R part Flush mounted base IP 54 IP 41 Optical parameters Value Wavelength 940 nm Operating distance 3 to 30 m Max E R corner misalignment 0 35 Max reflector corner misalignment 5 Max E...

Page 8: ...one B MAINTENANCE The specific equipment required for servicing the detector is A clean slightly damp cloth for cleaning the E R window and the reflector The alarm test filter to be positioned in fron...

Page 9: ...9...

Reviews: