INSTALLATION OF THE ELEMENTS 

The main detector installation steps are as follows: 

Step 

Step description 

Securing the detector base 

Electrical connections 

Securing the optical block 

Activating the laser pointer (press button) 

Securing the reflector 

Deactivating the laser pointer (press button) 

Caution: 

 

Leave a free area of at least 30 cm around each element installed on the wall. 

A.2.4.  Flush-mounted base 

The flush-mounted base is dedicated to 
recessing the E / R in a wall or dividing 
wall. 

 

 

 

 

The text on the base 

helps you position it 

correctly on the wall. 

A.2.5.  Surface-mounted base 

 

 

 

 

The text on the base 

(reference 3) helps 

you position it 

correctly on the wall. 

 

Summary of Contents for 48BFC000

Page 1: ...1 OPTICAL BEAM LINEAR SMOKE DETECTOR WITH REFLECTOR 3 30 M 48BFC000 Please read this manual before using the equipment and keep it safe for future reference...

Page 2: ...with national installation regulations Make sure both the detector and reflector can be accessed for commissioning and maintenance procedures A 2 2 Rules for the installation site The E R and the ref...

Page 3: ...Securing the reflector 6 Deactivating the laser pointer press button Caution Leave a free area of at least 30 cm around each element installed on the wall A 2 4 Flush mounted base The flush mounted b...

Page 4: ...ified the point indicated by the laser beam The reflector is secured in 2 steps Step 1 securing the safety reflector support Use screws with a maximum diameter of 4 mm to secure the safety reflector s...

Page 5: ...2 x 0 5 mm2 cables are recommended for COM COM and TL TL respectively The K terminal is connected by means of a wire from a 2 x 0 5 mm2 cable COMMISSIONING A 4 MAIN STEPS Commissioning takes place by...

Page 6: ...you press the button to deactivate the laser pointer make sure the detector and reflector are not exposed to direct sunlight Note If the orange light flashes after a succession of green pulses carry o...

Page 7: ...ection rating E R part Flush mounted base IP 54 IP 41 Optical parameters Value Wavelength 940 nm Operating distance 3 to 30 m Max E R corner misalignment 0 35 Max reflector corner misalignment 5 Max E...

Page 8: ...one B MAINTENANCE The specific equipment required for servicing the detector is A clean slightly damp cloth for cleaning the E R window and the reflector The alarm test filter to be positioned in fron...

Page 9: ...9...

Reviews: