A.1.
INTRODUCTION
The linear optical smoke detector consists of two parts positioned one in front of the other:
– An “Emitter/Receiver” part (E / R),
– A reflector consisting of 1 safety reflector.
A.2.
USAGE LIMITS
The linear smoke detector cannot be installed inside buildings.
OPTICAL BLOCK
1 fastener screws
2 built-in laser pointer
3 button
4 terminal connector
5 indicator light
SPECIAL EQUIPMENT
In addition to the normal tools supplied, the following is required:
– A piece of brown cardboard (packaging type) which can cover the whole surface of the reflector (minimum 10 cm
x 10 cm).
INSTALLATION RULES
A.2.1. General rules
Installation must be carried out in compliance with national installation regulations.
Make sure both the detector and reflector can be accessed for commissioning and maintenance procedures.
A.2.2. Rules for the installation site
The E / R and the reflector are installed vertically, one in front of the other, on a stable wall; this stability must take
account of the following parameters:
Smooth fixing wall; if it is uneven, use an intermediate support (for example, a 20 mm thick plywood plate).
The building must be stable (exclude unstable walls, cladding, etc.).
Ambient climatic conditions (for supports which could move in the event of wind, temperature changes,
condensation, etc.).
A.2.3. Optical rules
Do not expose the E / R and reflector to direct sunlight.
To accommodate the detector beam, provide a completely free circular area with a diameter of at least 60 cm; this is
necessary to ensure the product works properly.