Install the interior lighting lamp.
The product should be connected to the cold supply lines only by specialists of the manufacturer or organizations
having appropriate authorization (license) for this type of work.
Installation procedure:
a)
cut off the capped ends of the display case pipes with a length of 20-30 mm with a special tool and remove
the burrs;
b)
solder the joints, the silver content in the solder should be at least 5.5%;
c)
insulate the pipelines connecting to the cold supply lines.
For the remote unit pipeline connection diagram see Appendix C.
Warning: Do not move the display cases connected to the cold supply lines.
3.4 Pre-starting procedure of display cases
After the product is connected to the power supply as described above, it can be started from the control panel
(Fig. 3) and adjusted.
Note: pre-commissioning, network connection and controller configuration should be performed by a
representative of the Service Center certified for this type of work.
Warning: After transportation at a temperature below +10°C, keep the equipment at an ambient
temperature of +18°C to +25°C for at least 4 hours before switching on.
After a forced outage, the equipment should be reconnected to the power supply at least 3-4 minutes after its
disconnection. Load pre-cooled products only after the set temperature is reached in the display case interior.
DO NOT exceed the load limits!
Warning: Products and semi-finished products should be pre-cooled.
Products and semi-finished products should be uniformly arranged in plastic or stainless steel functional
containers. Place containers on demonstration trays and shelves loosely, with a clearance of at least 6 cm to the
walls. Load limits:
-
place products uniformly;
-
products should not block the air supply and intake openings;
-
products should not protrude beyond the shelves; the weight of products loaded on the shelf should
not exceed 120 kg / m² for a five-row display case, and for a six-row display case 100 kg / m²;
-
do not put boxes, bags etc. on the top of the refrigerated display case;
-
The condensate formed during evaporator defrosting should be drained to the sewer.
Commissioning, setting up of automatic control equipment of the refrigerating unit, maintenance and repair of
the product should be performed only by specialists of either the manufacturer or organizations appropriately
authorized (licensed) by the manufacturer for this type of work
Warning: Before sanitary treatment, routine maintenance and repair works, disconnect the display
case from the mains by removing the plug from the outlet, and remove the products from the display case interior.
Warning: Do not wash the product under running water, because accidental ingress of moisture to
electrical components can result in the product and the electrical safety system malfunction.