PARAMETER ADJUSTMENT
As delivered, the controller has the parameter settings specified in the Table 1. Parameter adjustment procedure:
•
press and hold the key (1) until the display shows the column with the code parameters;
•
select the desired parameter by pressing the keys (1) or (2);
•
press the key (3) to switch to parameter editing mode;
•
enter the desired parameter value by pressing the keys (1) or (2);
•
press the key (3) to record the value.
The controller will automatically exit the parameter setting mode if no keys are pressed.
Table 1. Default controller parameters.
Designation
Parameter specification, adjustment range
Value of
parameter
Unit of
measure
1
2
3
4
Temperature control
Interior temperature - set point (-50°С to +50°С)
Compressor deactivation temperature
-18, 0*, -6**,
1***, 4****
°С
r01
Temperature differential (0,1К - 20К)
Compressor is activated when the interior temperature exceeds the
previous set value + differential
3
°С
r02
Maximum limitation of setpoint setting (-49°С - +50°С)
5, 10***(****)
°С
r03
Minimum limitation of setpoint setting (-50°С - +49°С)
-21, -5* -6**.
0***(****)
°С
r04
Adjustment of temperature indication (- 20К - +20К)
0
К
r05
Temperature unit (°С/°F)
°С
°С/°F
r09
Correction of the signal from thermostat sensor (-10К – +10К)
0
K
r12
Manual service (-1), stop regulation (0), start regulation (1)
1
-
r13
Displacement of reference during night operation (-10К – +10К)
0
K
r39
Activation of reference displacement r40 (OFF – on)
OFF
-
r40
Value of reference displacement r40 (second range of the thermostat) (0 –
99 К)
0
K
Alarms
А03
Temperature alarm delay (0-240 min)
30
min
А04
Time delay for door alarm (0-240 min)
60
min
А12
Time delay for cooling (0-240 min)
90
min
А13
Upper alarm limit, at which the compressor is disabled within time "А03"
(-50 - +50 °С)
10, 15***(****)
°С
А14
Lower alarm limit, at which alarm is raised (-50 - +50 °С)
-25, -5***(****)
°С
А27
Delay of a DI alarm (0 - 240 min)
30
min
А37
High alarm limit for condenser temperature (0 - 99 °С)
50
°С
Compressor
c01
Minimum ON-time (0 min - 30 min)
0
min
c02
Minimum OFF-time (0 min - 30 min)
2
min
c30
Compressor relay must cutin and out inversely (NC function) (0/OFF –
1/On)
0/OFF
-
C70
Zero crossing control – only EKC302
On
-
Defrosting
d01
Defrosting method (no/gas/EL )
EL
-
d02
Defrost stop temperature (0°С – 25°С)
15, 8****
°С
d03
Interval between defrost starts ( 0 - 48 h)
4, 12****
h
d04
Maximum defrost duration (0 - 180 min)
30, 15***
min
d05
Displacement of time on cutin of defrost at start-up (0 – 240 min)
0
min
d06
Drip off time (0 – 60 min)
2
min
d07
Delay for fan start after defrost (0 -65 min)
3
min
d08
Fan start temperature (-15 – 0 °С)
-3
°С