19
www.combisteel.com
d09
Fan cutin during defrost
0, 1***(****)
-
d10
Defrost sensor (0 – time /1 – S5 /2 - Sair)
1, 0***
-
d18
Maximum aggregate refrigeration time between two defrosts (0 – 48 h)
0
-
d19
Defrost on demand - S5 temperature’s permitted variation during frost
build-up (20К = Off)
20
K
Fan
F01
Fan stop at cutout compressor (no/yes)
no
-
F02
Delay of fan stop (0 – 30 min)
0
min
F04
Fan stop temperature (S5) (°С )
10
°С
Real-time clock t01-t47
Miscellaneous
o01
Delay of output signals after start-up (0 – 600 sec)
5
sec
о02
Digital input function:
0 – not used; 1 – door function; 2 – defrost start;
3 – external alarm; 4 – night operation
0
-
о03
Network address - for EKC302 only (0 – 240)
1
-
о04
Service message – for EKC302 only
OFF
-
o05
Access code (0 – 100)
0
-
o06
Used sensor type (Рt/ntc- 5 kOhm)
ntc
-
о15
Display step =0.5 (normal 0.1 at Pt sensor)
(no – yes)
no
-
о16
Maximum hold time after coordinated defrost.
20
-
o46
Cleaning
0
-
o64
Access code 2 (partly access) (0 -100)
0
-
о67
Replace the controllers factory settings with the present settings
(OFF-On)
OFF
-
o70
Alternative application for the S5 sensor:
(0 – defrost sensor; 1 – product sensor; 2 – condenser sensor)
0
-
Service
u09
Temperature measured with S5 sensor
-
-
u10
Status on DI1 input (on/1 = closed)
-
-
u13
Status on night operation (on or off)
-
-
u28
Read the present regulation reference
-
-
u58
Status on relay for cooling
-
-
u59
Status on relay for fans
-
-
u60
Status on relay for defrost
-
-
u69
Temperature measured with Sair sensor
-
-
Note: Parameter values:
- for low temperature cabinets, monoblocks and split systems;
* - for medium temperature monoblocks and split systems;
** - for DP102 cabinet.
*** - for medium temperature cabinets.
**** - for refrigerated wall display cases