Digital fire detection control panel 

COMPACT LYON PLUS 

 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for COMPACT LYON PLUS

Page 1: ...MANUAL Digital fire detection control panel COMPACT LYON PLUS ...

Page 2: ...A2Y 24 1 5 4 6 Two relay dry contact output module MDA2YLT 26 1 5 4 7 Module to connect 32 detectors 10 manual call points KMAY32 27 1 5 4 8 Module with 8 inputs MSTAY8 28 1 5 4 9 Loop isolator KABY 30 1 5 4 10 Addressable sounder SIRAY SIRAYL SIRAY BSLC 31 1 5 4 11 Remote indicator PIAL 32 1 5 4 12 Base with siren and visual alarm A50ZSLDR A50ZSDDR 33 1 5 4 13 Base with siren and visual alarm A30...

Page 3: ...me message 66 3 2 2 11 General reset rearm 66 3 2 2 12 Review history 66 3 2 3 Level 3 access 67 3 2 3 1 Access code 67 3 2 3 2 Label points 68 3 2 3 3 Configure 68 3 2 3 3 1 Loop configuration 68 3 2 3 3 2 Logic In out configuration 69 3 2 3 3 2 1 Configure logical relays 70 3 2 3 3 2 2 Relay Auto Configuration 72 3 2 3 3 2 3 Delete Configured Relays 72 3 2 3 3 3 Configure alarm zones 72 3 2 3 3 ...

Page 4: ... the incident 86 5 Evacuation 87 6 SILENCE SIRENS 87 7 RESET EVENTS 87 Annex 2 Elements configuration Lyon C Lyon Zafir 88 1 Introduction 88 2 Keypad access 89 3 Configuration of points in a loop 90 3 1 System Programming 90 3 2 Configure 90 3 3 Configure Loop 91 3 4 Loop Configuration 91 3 5 Assign a number to Point 92 4 Programming verification process 92 5 Configure Zones 93 6 Replacing a loop ...

Page 5: ...bility of operational reliability Vibration resistance Cumple Passed Duración de la seguridad operacional y retardo a la respuesta estabilidad eléctrica Durability of operational reliability electrical stability Cumple Passed Duración de la seguridad operacional y retardo a la respuesta resistencia a la humedad Durability of operational reliability humidity resistance Cumple Passed EN 54 4 Equipo ...

Page 6: ...concentration and the amount of monoxide are sent through the corresponding sensor in electrical voltages related to the measured magnitude After an adaptation process an optimal relationship between the measured magnitude and the electrical voltage is obtained Each sensor incorporates a microprocessor responsible for the digitisation of the analogue value read in the sensor for transmission of th...

Page 7: ...n of up to 15 repeaters and 15 control panels in network Contact ID See specific manual of this functionality Cofem Remote on demand Size 363 x331 x 96 mm IP30 Certified and CE mark according to EN 54 2 and EN 54 4 Standard 1 4 Composition of the control panel Backlit LCD display of 4 lines and 40 characters Keyboard made up of 13 keys that form two groups one where the menu handling keys can be f...

Page 8: ... in the program It allows calculation of complex element distribution situations or open line operation The software returns the electrical load of the system in number of equivalent elements and relays in the loop It must not be exceed the limits establieshed in the Maximum devices per control panel table loop limits and control panel limits INSTALLATION EXAMPLE An installation requires 72 A30XHA...

Page 9: ...TURER C Compositor Wagner 8 P I Can Jardí 08191 RUBÍ Barcelona ESPAÑA Tlf 34 935 862 690 cofem cofem com www cofem com Note Indicative table Highly recommend using the loop element capability software for references not listed in this table or to view optimized loop configurations ...

Page 10: ...Digital fire detection control panel COMPACT LYON PLUS 10 FIRE PROTECTION MANUFACTURER C Compositor Wagner 8 P I Can Jardí 08191 RUBÍ Barcelona ESPAÑA Tlf 34 935 862 690 cofem cofem com www cofem com ...

Page 11: ...rosols makes it suitable as smoke sensors The sensor element is formed by an optical chamber provided with an infrared emitter and receiver In the absence of smoke the intensity of infrared caught by the receiver is null due to the physical labyrinth created between the two When smoke is present the infrared reflections from the particles of the same cause the receiver to obtain a certain luminanc...

Page 12: ...chosen degree Also in the detection of temperature confirmation by means of two consecutive readings is used less than 10 seconds before activation of the Alarm The operation principle is based on the physical properties of an NTC The variation in electrical characteristics of the thermistor due to the variation of the room temperature is what enables its use as a sensor element The measurement ma...

Page 13: ... null due to the physical labyrinth created between the two When smoke is present the infrared reflections from the particles of the same cause the receiver to obtain a certain luminance intensity Voltage value proportional to the level of obscuration all of which is controlled by the microprocessor system In addition it has a carbon monoxide sensor with a fast response in the presence of CO which...

Page 14: ...nel COMPACT LYON PLUS 14 FIRE PROTECTION MANUFACTURER C Compositor Wagner 8 P I Can Jardí 08191 RUBÍ Barcelona ESPAÑA Tlf 34 935 862 690 cofem cofem com www cofem com Figure 2A Wiring Diagram of A30XHA A30XTA A30XHTCO and PUCAY devices ...

Page 15: ...With short circuit isolator Low profile total height less than 55 mm including low base Also available with high base for 20 mm tube Possibility of connection to a remote action indicator Easy connection Bicolor red and yellow LED Indication by means of the red LED of the communication with the control panel single flashing as well as of the alarm status LED on Indication by means of the yellow le...

Page 16: ... 42 mm including low base Also available with high base for 20 mm tube Possibility of connection to a remote action indicator Easy connection and A50S without polarity Bicolor red and yellow LED Indication by means of the red LED of the communication with the control panel single flashing as well as of the alarm status LED on Indication by means of the yellow led single flash of the activation of ...

Page 17: ...mote action indicator Easy connection and A50S without polarity Bicolor red and yellow LED Indication by means of the red LED of the communication with the control panel single flashing as well as of the alarm status LED on Indication by means of the yellow led single flash of the activation of the short circuit isolator or the lack of communication with the control panel Signaling of the dirty st...

Page 18: ...cator Simplified connection diagram A50S does not require polarity Bicolor led Red and Yellow Indication by means of the red led of communication with the control panel single flashing as well as of the alarm status led on Indication by means of the yellow led single flash of the activation of the short circuit isolator or the lack of communication with the control panel Signaling of the dirty sta...

Page 19: ...Compositor Wagner 8 P I Can Jardí 08191 RUBÍ Barcelona ESPAÑA Tlf 34 935 862 690 cofem cofem com www cofem com Figure 2B Schematic diagram for the A50 family and PUCAY NOTE If the detector has ISOLATOR the POLARITY must be RESPECTED B negative A1 loop input positive B2 loop output positive ...

Page 20: ...ion with the Control panel Lyon system and if it remains on it indicates the alert status of the button There is a version PUCAYEXT that it is computed by control panel as the activation of 2 simultaneous devices In this way the configured relays can be triggered directly when acting on this version of the switch From loop device capacity PUCAYEXT version is considered identical as a PUCAY The PUC...

Page 21: ... between conventional smoke detectors A30XH A30XHS and manual call points Both terminals are monitored by an end of line capacitor 10 µF 63V In this way the status of the line can be known if it is open shorted to ground or a device entered in alarm state The flashing of the transparent red LED indicates communication with the control panel and if it remains on it indicates the alarm status of a d...

Page 22: ...quiescent condition the device monitors the electrical connection through a 33 K resistor which allows indication of open or closed electrical connection status It is typically used to signal the status of other detection systems that may exist as for example connection of flow sensors in the case of sprinkler installations end of travel in the case of fire resistant doors elevators level of depos...

Page 23: ...gnal input has a 10 K resistor connected in series with the dry contact In quiescent condition the contact has to be open and in anomaly condition the contact has to be closed In the input marked with IN2 the closed contact is detected as ALARM condition The MYOA supervises each external line relay ouput and technical signal input through a 33 K each one which allows indication of open or closed e...

Page 24: ...installation of an External Power Supply when connecting more than 10 electromagnets altogether per detection system The MDA1Y device complies with EN 54 18 with the conformity mark awarded by AENOR Note To determine the number of MDA1Y devices that can be installed in a loop consult the devices limit per control panel table Chapter 1 5 1 5 4 5 Master relay module MDA2Y Microprocessed addressable ...

Page 25: ...l panel COMPACT LYON PLUS 25 FIRE PROTECTION MANUFACTURER C Compositor Wagner 8 P I Can Jardí 08191 RUBÍ Barcelona ESPAÑA Tlf 34 935 862 690 cofem cofem com www cofem com Figure 6 Wiring diagram MDA1Y Figure 7 Wiring diagram MDA2Y ...

Page 26: ... are powered by the loop connection requiring no outside power The blinking red transparent LED shows there is communication with the control panel The fixed lit red transparent LED indicates that one or both relays have been triggered To order rectangular boxes made of heat resistant ABS are available This is a module with two relay outputs that are separately activated two functions independent ...

Page 27: ...en smoke detectors A30XH A30XHS and conventional alarm call points Both strips supervise the line using a 4K7end of line resistor It thus indicates the status of the open line crossed line detector alarm or alarm call point alarm It has a microswitch for setting the area thresholds Open line threshold pin microswitch 1 2 Detector alarm triggered threshold pin microswitch 3 4 Alarm call point trigg...

Page 28: ...stor indicating the status of the line or crossed line Connecting a parallel 10kΩ resistor will activate the related input Active by closed contact pin 1 microswitch set to OFF and pin 3 microswitch set to OFF the input in standby must be with the contacts open in case of event the input contacts must be crossed This will be the factory settings Active by open contact pin 1 microswitch set to OFF ...

Page 29: ... control panel COMPACT LYON PLUS 29 FIRE PROTECTION MANUFACTURER C Compositor Wagner 8 P I Can Jardí 08191 RUBÍ Barcelona ESPAÑA Tlf 34 935 862 690 cofem cofem com www cofem com Figure 10 MSATY8 wiring diagram configurations ...

Page 30: ... line failures and allowing therefore the rest of the loop to operate normally It is supplied installed inside of a high base This assembly allows having it in the same place as the sensor making easy the connection of the loop wiring The base has two stickers in the outer side with the word KABY to allow easy recognition The element is feed from the loop connection The KABY is conformant with EN ...

Page 31: ...cally does not affect the programming of control panel For this reason these devices are programmed in the control panel as it was SIRAY The standard configuration of the sound of the siren is shown in Figure 12 according to EN 54 3 sounder In the same figure the standard configuration of the light signal in the socket of the SIRAY BSLC siren according to EN 54 23 visual alarm device is shown It i...

Page 32: ...nge for the identification of the element in alarm for example in hotel rooms where the PIAL can be situated above the door frame of each room making very easy its identification Permanent activation of the red LED indicates alarm status It is an element easy to install both for its electrical wiring and its fixation Furthermore it can be adapted to the conduit boxes and switchgear Features Alarm ...

Page 33: ...ent with siren and visual alarm such as hotel rooms equipped for clients with hearing impairments waiting rooms nursing rooms etc The coverage of the set should not be greater than the coverage of the fire sensor with which it is installed except for reasons that justify it Functionally the sensor is wired according to the criteria of the fire panel to which it is connected Two models are availabl...

Page 34: ...E PROTECTION MANUFACTURER C Compositor Wagner 8 P I Can Jardí 08191 RUBÍ Barcelona ESPAÑA Tlf 34 935 862 690 cofem cofem com www cofem com Figure 14A Wiring diagram A50XZSDDR A50XZSLDR Figure 14B Configuration DIP A50XZSDDR Figure 14C Configuration DIP A50XZSLDR ...

Page 35: ...age of the set should not be greater than the coverage of the fire sensor with which it is installed except for reasons that justify it Functionally the sensor is wired according to the criteria of the fire panel to which it is connected Two models are available A30XZSLDR Base Socket with light and sound addressable A30XZSDDR Base Socket with sound addressable A diode is embedded in socket Notes T...

Page 36: ...E PROTECTION MANUFACTURER C Compositor Wagner 8 P I Can Jardí 08191 RUBÍ Barcelona ESPAÑA Tlf 34 935 862 690 cofem cofem com www cofem com Figure 14A Wiring diagram A30XZSDDR A30XZSLDR Figure 14B Configuration DIP A30XZSDDR Figure 14C Configuration DIP A30XZSLDR ...

Page 37: ...es for the RS485 line must be connected from the connector indicated as REPETIDOR at the Control Panel with each connector of the repeaters indicated as REPETIDOR on the label The two power supply wires must be connected from the 30 V output of the Control Panel power supply with the connector indicated with 30 VDC in each repeater Figure 11 shows this wiring diagram It can be used the C Lyon cont...

Page 38: ...igured To do this follow this sequence in the control panel Menu access code 27 4 System setup access code 9000 8 Communications 1 Repeater network 2 Configure repeaters Control_Panel_Menu After configuring the control panel a number must then be assigned to each repeater This must be the same as the one which was configured in the control panel To do this follow this sequence in the corresponding...

Page 39: ...en be sent according to this sequence in the control panel Menu access code 27 4 System Setup access code 9000 2 Configure 9 Send Zones to Repeaters Control Panel Menu Functions that can be carried out from the repeater Reset alarms and faults RESET Activate or deactivate silence sounders Activate or deactivate evacuation Activate or deactivate manual mode Activate or deactivate delays Deactivate ...

Page 40: ...arian Ukrainian and Portuguese pre installed at factory 1 3 REPEATER NUMBER From this menu the repeater number to be used when communicating with the control panel can be selected This number can never be used in more than one repeater 2 GENERAL REARM From this option the whole system can be reset When the system is reset all the events are deleted from the control panel and the repeaters i e alar...

Page 41: ...n control panel COMPACT LYON PLUS 41 FIRE PROTECTION MANUFACTURER C Compositor Wagner 8 P I Can Jardí 08191 RUBÍ Barcelona ESPAÑA Tlf 34 935 862 690 cofem cofem com www cofem com Figure 16 Repeater connection diagram Max 15 ...

Page 42: ...2 RS485 communication line The two wires of the RS485 line will be connected from the CP NETWORK indication in the CPU card of each control panel This connetion is shown in figure 18 Power is held in each control panel separately Each control panel will be connected to the 110 230V mains and its corresponding set of batteries The communication cables connection between control panels will be made ...

Page 43: ...enu_Control_Panel After the configuration should perform a general reset at each control panel of the network For this we perform the following sequence Menu code 27 8 General reset A control panel in the network can perform the same functions as any normal control panel You can also perform the following functions on the rest of the control panels of the network Reset alarms and faults in the net...

Page 44: ...ctivated deactivated by another Control Panel connected in the panel network SET CONTROL PANEL NUMBER Every central must have a unique number in network Number accepted are between 1 35 but max number of repeater is 15 and 15 control panels VIEW CONTROL PANEL NUMBER View the current central number NOTE Is due to connect a resistance of 120 ohms between the connectors A and B of the connected strip...

Page 45: ...ircuit faston and the connector of the CPU with the output circuit See figure 29 end of the manual chapter 4 Any connection or movement of the control panel must be carried out with the panel disconnected both from the power supply and from the batteries 2 2 C Lyon system connection Connection of the C Lyon addressable system will be carried out with 2 x 0 7 mm up to 2 x 2 5 mm BRAIDED CABLE SCREE...

Page 46: ... following table Loop 01 POINT Programming no Label Type Notes 1 12757 ROOM 101 A30XHA 2 12432 ROOM 102 A30XHA 3 4767 BUTTON P1 PUCAY 4 6982 CORRIDOR P1 MDA1Y DISCONNECT the 110 230V Voltage circuit and BATTERIES before accessing the interior of the control panel 2 2 1 Electrical supply network Power supply is 110 230V 10 50 60 Hertz Connection will be made by means of 3 strands with a minimum sec...

Page 47: ... addressable system will be carried out with 2 x 0 7 mm up to 2 x 2 5 mm BRAIDED CABLE SCREENED HALOGEN FREE for lenght between the elements and the control panel of lengths of up to 1500 meters Connection will be made according to Figure 24 General wiring diagram DISCONNECT the 110 230V Voltage circuit and BATTERIES before accessing the interior of the control panel 2 2 3 Power supply auxiliary o...

Page 48: ...essable modules or relays or other external devices This output is monitored and protected by means of a fuse 2 3 Components 2 3 1 Batteries Power supply _ The supervised battery input output allows the connection of batteries to the control panel The batteries are charged through this connection as well as the monitoring of its status The battery charge is compensated depending on the temperature...

Page 49: ...tection control panel COMPACT LYON PLUS 49 FIRE PROTECTION MANUFACTURER C Compositor Wagner 8 P I Can Jardí 08191 RUBÍ Barcelona ESPAÑA Tlf 34 935 862 690 cofem cofem com www cofem com Figure 24 General Wiring Diagram ...

Page 50: ...e control panel and or modules 1 Diode BY252 two diodes are included with each control panel system Figure 25 SIR 24B BL connection schematic 2 3 3 2 Connection of the non flashing internal 24V Sounder SIR24P Elements needed for its correct installation 1 Resistance of 33 KΩ in the event of the sounder being connected to the general sounder the resistance should be 4K7 which is included in the con...

Page 51: ...er the resistance should be 4K7 which is included in the control panel and or the modules 1 BY252 Diode two diodes are included with each control panel Figure 27 SIR24F Connection schematic 2 3 3 4 External Siren 24V alarm box CAEC Red outdoor siren made of ABS plastic Built in back cover to protect all internal circuitry They work as 24V power sirens Piezoelectric speaker Certified EN54 3 type B ...

Page 52: ...1 8 GHz Windows 7 8 10 2 GB of RAM 1 GB of free space in HDD DirectX9 minimum resolution of 1024x768 Free USB port As shown in the diagram the connection between the PC and the control panel must be made using a USB 2 0 PORT The use of the I Link program and the configuration of the communication ports of the computer are described in the manual Manual I Link In the case of installing the function...

Page 53: ... FIRE PROTECTION MANUFACTURER C Compositor Wagner 8 P I Can Jardí 08191 RUBÍ Barcelona ESPAÑA Tlf 34 935 862 690 cofem cofem com www cofem com Example of PC I Link ONLINE connection for long distances Through a RS232 RS485 converter or using TCP IP connection ...

Page 54: ...en and to select characters in text mode ESC Key that enables the user to pass from one level to a higher level in the menu tree of the control panel and to cancel menu selections MENU This key enables us to enter the control panel menu and to show the help text of the various menus ENTER This key enables us to confirm a selection SILENCE BUZZER RESET Key that enables the user to reset events that...

Page 55: ... f i r C o f e m s a MO D E MO D E 1 2 0 8 0 6 N I G H T A U T O M A T I C 1 0 2 9 3 2 Access levels The control panel has four levels of access Level 1 allows the control panel to be manipulated in its most basic functions such as silencing the buzzer or review of the incidences that the control panel has been able to detect Level 2 it is only accessible by maintenance personnel by means of the a...

Page 56: ...a type 4 2 1 2 Blink 4 2 1 2 1 Blink enabled 4 2 1 2 2 Blink disabled 4 2 1 2 3 View setup 4 2 1 3 Set up Loop Points 4 2 1 3 1 View loop information 4 2 1 3 2 Loop points Search 4 2 1 3 3 Assign Point number 4 2 1 3 4 Loop Automatic Configuration 4 2 1 3 5 Delete Point 4 2 1 3 6 Change point 4 2 1 3 7 Delete Loop Points 4 2 2 Logic In out configuration 4 2 2 1 Logic relays configuration 4 2 2 1 1...

Page 57: ...ay time start 4 4 2 Day time end 4 4 3 Set up Days Night Mode 4 4 4 Delete programmed Night Mode 4 4 5 Set up Summary 4 5 Swap test normal 4 5 1 Test mode 4 5 1 1 General 4 5 1 2 Zone Test 4 5 2 Normal mode 4 5 2 1 General 4 5 2 2 Zone Test 4 5 3 Zone List 4 6 Led ON OFF 4 6 1 Led ON 4 6 2 Led OFF 4 7 Language menu 4 7 1 Set language to Spanish 4 7 2 Set language to English 4 7 3 Set language to F...

Page 58: ...2 1 Activate 4 8 8 2 2 Deactivate 4 8 8 3 IP 4 8 8 4 PORT 4 8 8 5 MASK 4 8 8 6 GATEWAY 4 8 8 7 UMIP 4 8 8 8 Serial Number 4 9 Sounder stop function 4 9 1 Activation 4 9 1 1 Continued 4 9 1 2 Reset 4 9 2 Performance 4 9 2 1 Continued 4 9 2 2 Event 4 9 3 View setup 5 Enable disable points zones 5 1 Enable point 5 2 Disable point 5 3 Enable zone 5 4 Disable zone 5 5 List disabled zones 6 System Test ...

Page 59: ...panel has been initialized correctly and that no alarms or faults of any type exist in the system Only the green LED is illuminated Power It is also possible that other screens appear indicating anomalies of some type that are described in the following cases C D I C Z a f i r C o f e m s a MO D E MO D E 1 2 0 8 0 6 N I G H T A U T O M A T I C 1 0 2 9 Anomalies during start up 1 During the startin...

Page 60: ...rs The first line of the alarm corresponds to the selected alarm whereas the second field refers to the last alarm received A L A R M S T Y P E 0 1 L A B E L M C P T 0 1 0 1 If the right cursor is pressed we will be able to see the rest of the alarm information Unit Loop POINT A L A R M S C B P t 0 1 Z 0 0 1 L A B E L 0 1 0 1 0 0 6 0 1 0 2 Nº of alarmed zone Selected alarm Nº alarms Relays on If t...

Page 61: ...tects a power supply failure it will illuminate the amber GENERAL FAULT and SUPPLY FAULT LEDs sound the buzzer and show the following message F A U L T S T Y P E 0 1 S U P P L Y C O N T R O L 1 1 E M P T Y B A T 0 2 S U P P L Y C O N T R O L 1 1 H I G H V N E T 0 1 0 2 Within supply faults the following types of fault exist Type of Fault Description 30V Fault in the 30V output NO BATTERY Battery f...

Page 62: ...t in the loop They aslo can report the dirty sensor fault except A50HI A50HI A50SHI A50HSCOI General sounders faults If the control panel detects a failure in the power supply to any of the two general sounder it will illuminate the amber GENERAL FAILURE LED sound the buzzer and show the following message F A U L T S T Y P E 0 1 P O W E R S U P P L Y S C R E L A Y 0 1 0 1 0 1 Relay number In this ...

Page 63: ...topped after it has been activated by an incident It is automatically reactivated for each new incident 3 2 2 Level 2 access 3 2 2 1 Access code P a s s w o r d L e v e l 2 0 0 When pressing the menu key we access level 2 by means of a code 027 At this new level we will be able among other things to deactivate incidents to put zones into service to disable zones and to activate and deactivate rela...

Page 64: ...s 0 0 1 N P r o g 5 5 8 2 6 V a l u e s 0 0 0 0 0 0 0 0 0 0 0 0 T e m p 0 2 5 D i r t 0 0 0 A v e r a g e 0 0 0 S e n s i t i v M E D In the case of a thermal sensor the values are monitored in degrees L A B E L T y p e A 3 0 X T A L o o p 0 0 1 A d r e s s 0 0 1 N P r o g 5 5 8 2 6 V a l u e s 0 2 5 0 2 5 0 2 5 0 2 5 T e m p 0 2 5 D i r t A v e r a g e 0 0 0 S e n s i t i v M E D 3 2 2 5 Activate...

Page 65: ...evel 3 access we are able to access the configuration menu See chapter 3 2 3 Level 3 access 3 2 2 8 Enable Disable elements and zones Menu_5 Exactly as they suggest the submenus enable us to enable disable zones or elements individually and to view a list of the out of service zones 3 2 2 9 System test Option_6 Option 6 of the main menu SYSTEM TEST This is an option that allows us to perform a tes...

Page 66: ...el events are deleted that is to say alarms faults and actuations It maintains the state of the out of service elements and or zones 3 2 2 12 Review history Option 9 of the main menu In this menu we have 5 submenus REVIEW COMPLETE HISTORY REVIEW ALARMS REVIEW FAULTS REVIEW DISABLED ITEMS and REVIEW RELAYS By means of the up and down cursors we will move through the various stored events The events...

Page 67: ...0 1 L A B E L B 3 P 3 N S 3 Review disabled items This submenu is the same as the one to review the complete history except that is exclusively for disabled items Type of event Diasabled type N U M 0 0 1 D I S A B L E D D I S E L E M E N T L O O P 0 1 P O I N T 0 0 1 N P r o g 0 0 1 2 0 Z O N E 0 1 C P A N E L 0 1 0 1 0 1 0 7 1 2 0 1 L A B E L B 1 P 1 N S 1 2 0 Review relays This submenu is the sa...

Page 68: ...T E R A C C E P T 3 2 3 3 Configure Menu_9 Option 2 of the SYSTEM CONFIGURATION menu 3 2 3 3 1 Loop configuration Menu_17 In this menu we have the possibility of configuring all the parameters related to the element of a loop such as to assign the element numbers to detect the elements to configure sensitivity etc Within the LOOP CONFIGURATION menu we have three important submenus that are SENSITI...

Page 69: ...ted in a loop The control panel must know this programming number to identify the elements AUTOMATIC LOOP SETUP Find the points of the loop and assigns a setup number to each point in order of programming numbers starting with the smallest DELETE POINT To delete a point that is no longer connected to the loop and is still configured delete the programming number and the label of the element REPLAC...

Page 70: ...econds is possible DAY NIGHT In this submenu we can configure the type of activation of a logical relay active with or without delay inactive for a daytime and night schedule We will be able to activate the day mode independently for every day of the week PHYSICAL SITUATION Loop and point number where the logical relay is LABEL To introduce a description of the relay for its identification in the ...

Page 71: ...1 L A B E L 1 C T R L 0 1 L O O P 0 1 A L R M 1 P N T S 0 0 1 0 0 1 2 C T R L 0 0 L O O P 0 0 A L R M 1 P N T S 0 0 5 0 0 5 3 C T R L 0 0 L O O P 0 0 A L R M 0 P N T S 0 0 9 0 0 9 In this case the RELAY_01 will be activated by Control_Panel_01 from LOOP_01 when sensor 1 5 and 9 are all of them in alarm state and our relay may be in that loop or another Very important to notice is the logic operato...

Page 72: ... this menu we have the option of configuring the various alarm zones into which we will divide the points of the control panel When an alarm zone is configured it is not permissible to include a point in two different alarm zones Within this menu we have five submenus CONFIGURE ZONE The control panel will request the loop number the first and last consecutive element included in the alarm zone lis...

Page 73: ... we introduce a new password it deletes the one that had been previously entered The standard Passwords that the control panel have are access level 2 27 and access level 3 9000 3 2 3 3 6 Configure auto evacuation Menu_9 Within this menu we have four submenus ENABLE AUTOEV DISABLE AUTOEV CONFIGURE DELAY and AUTO EVACUATION SUMMARY Automatic evacuation is a function that activates the relays config...

Page 74: ...duced in this option makes immediately activation of all control panel relays 3 2 3 3 9 Send Zones to Repeaters Menu_9 This option allows sending the configured zones to the repeaters if not executed the repeaters will only indicate the label of the point 3 2 3 4 Update date and time Menu_10 Within this menu we have two options CHANGE DATE and CHANGE TIME With the cursors we will be able to update...

Page 75: ... this menu we have two options we will be able to activate normal mode generally or by alarm zone LIST ZONES This option shows us the operating mode of the control panel and the alarm zones 3 2 3 7 Led ON OFF Menu_13 This is option 6 of the SYSTEM CONFIGURATION menu This menu allows activation or desactivation If it is already activated the led of one element of the loop This functionality is acti...

Page 76: ...is menu the connected repeaters are detected and the control panel will automatically communicate with these repeaters ERASE REPEATER From this option the selected repeater is deleted DELETE REPEATERS From this option all the repeaters configured in the control panel are deleted LABEL REPEATER In this menu we give a label to the repeater with a maximum of 20 characters CONTROL PANEL NETWORK SEE CO...

Page 77: ... THE CONTROL PANEL NUMBER TYPE OF PC COMMUNICATION The communication ports of the control panel are configurable with the different available functionalities The control panel has 3 RS485 communications ports identified as CONPC COM1 CONRED COM2 CONREP COM3 and a USB port identified as USB USB1 In this menu you can select the port you want to use with the following features NeTW Connection port fo...

Page 78: ...es By default the value of the mask is 255 255 255 0 GATEWAY IP address of the server router By default the value is 192 168 0 50 DHCP allow automatic configuration of IP PORT and MASK UMIP Acronym for Update My IP With the activation of this function it is allowed to communicate with the REMOTE card of the central from the web www l remote com automatically without needing to know the IP address ...

Page 79: ...th connection errors that could cause faults when putting into operation or deterioration of the C Lyon digital system elements Do not remove the covers until the installation is finished and clean To have a list with the total of connected elements of each type in each loop see example in the following table LOOP 1 TYPE AMOUNT A30XHA 15 A30XVA 2 A30XHTCA 5 PUC AY 10 SIRAY 1 MDAXY 6 MSTAY 1 KMAY 3...

Page 80: ...t them programming numbers labels to be able to complete the putting on operation If the number found is lower it means that fewer elements have been installed in the loop there are unconnected or not assembled loop elements Review the whole loop installation reviewing all the connections and counting the installed elements Once all problems in the system have been solved the loop element search m...

Page 81: ...tery is not connected to the control panel Cause Either the battery is not connected to the control panel or it is connected incorrectly Solution Check that the batteries are correctly connected to the control panel and check the status of the battery output fuse 5 Amps Carefully examine the battery polarity and check that they are connected in series For normal operation the voltage in the batter...

Page 82: ... the end of line resistance 4K7 and check the supervision diodes are correctly mounted see chapters 2 3 3 1 and 2 3 3 2 To operate correctly the S1 General Sounder s output voltage must be between 10V and 18V when in standby and between 24V and 29V when activated 4 3 LOOP FAULTS ELEMENT NOT RESPONDING Cause An element in the loop has stopped working Solution Check that the element has not been rem...

Page 83: ...rrectly mounted see chapters 1 5 4 4 1 5 4 5 and 1 5 4 3 voltage of the relay 1 of the MDA1Y MDA2Y or MYOA must be between 2 V and 7 8 V when in standby and between 24 V and 29 V when activated RELAY SHORT CIRCUIT 01 Short circuit for the relay 1 of MDA1Y MDA2Y or MYOA Cause There is a short circuit between the output of the relay 1 of the MDA1Y MDA2Y or MYOA and the end of line resistance Solutio...

Page 84: ... V and 7 V in rest OPEN CIRCUIT 02 Open line in MSTAY or MYOA input 2 Causa There is a lack of continuity between the entrance 2 of the MSTAY or MYOA and the end of line resistance Solución Verify the correct connection between the MSTAY MYOA and the elements connected to them verify the end of line resistance 33 K see 1 5 4 2 and 1 5 4 3 chapters The tension of entrance 2 of the MSTAY for a corre...

Page 85: ...red making sure that the number configured in the control panel is the same as the repeater s number see chapter 3 2 3 9 CONTROL PANEL XX IS NOT COMMUNICATING Cause There is a failure communication with the indicated control panel Solution Check the connection of the control panel with the main control panel check short circuits cut cables check the correct operation of the control panel see 1 5 5...

Page 86: ...warning of the event and acting on various elements such as emergency exit doors acoustic fire alarms or crossed outputs 2 Front panel of the system This is how the control panel of the systems looks like The keys enable action to be taken via the control unit while the luminous indicators LEDs and the screen provide information about the system status 3 What happens if the buzzer sounds The buzze...

Page 87: ...tion can be performed once the keypad has been enabled and by pressing the evacuation key IMPORTANT This must be confirmed with the ENTER key This function activates all sirens and switches in the system This is also shown by lighting the luminous indicator 6 SILENCE SIRENS When required this function enables the sirens to be silenced The keypad must be enabled and it is performed by pressing the ...

Page 88: ... PUCAY Master module KMAY Relay modules 1 relay MDA1Y 2 relay MDA2Y Technical signals module MSTAY MSTAY8 Relay and Technical signal module MYOA F Loop isolator base KABY Addressable siren SIRAY SIRAYL SIRAY BSLC Each of these elements has a programming label This number is assigned at the factory When an element search operation is conducted using the control unit it finds all the loop elements s...

Page 89: ...code will be requested AN ACCESS CODE WILL BE REQUESTED Nº 27 IMPORTANT If no key is pressed within a period of 30 seconds the keypad is blocked and the previous step must be repeated in order to continue using the keypad As soon as keypad access has been provided all keys can be used immediately SIN RETARDO NO DELAY PARO SIRENAS SILENCE SOUNDERS ALARMA ALARM DESCONEXIÓN GENERAL DISABLE MODO PRUEB...

Page 90: ...n will show the main menu on the display KEYS FOR NAVIGATING THE MENUS ESCAPE KEY ENTER KEY Return to previous screen Confirm menu options By using the arrow keys the menu options below will be displayed 3 1 System Programming By selecting option 4 System Configuration the access code for level 3 will be requested Enter the code and confirm with the ENTER key AN ACCESS CODE WILL BE REQUESTED Nº 90...

Page 91: ... Set up loop Points the option will be the first to appear Confirm with the ENTER key The following menu with 7 options will appear on the display By selecting option 2 Loop points Search the option will be the first to appear Confirm with the ENTER key Confirm with ENTER Menu code 27 4 System setup 2 Configure 1 Loop configuration 3 Set Up Loop Points 2 Loop points Search This function passes all...

Page 92: ... Important In order to proceed with this operation the installer must have made written note of the programming number of each of the sensors and the loop in which they are installed Firstly you will be asked for the programming number of the corresponding Point confirmed with the ENTER key Secondly you will be asked for the assigned Point number confirmed with the ENTER key 4 Programming verifica...

Page 93: ...a zone is to group together sensors that are located in the same area In order to configure alarm zones it is necessary to follow the following steps Menu access code 27 4 System configuration access code 9000 2 Configure 3 Configure Alarm Zones You will be asked for the number of the zone to configure Enter the number and the following menu will appear By selecting option 1 Configure Zone the opt...

Page 94: ...0 7 A 5 0 H I 0 0 0 0 0 1 M D A x Y 0 0 0 A 3 0 X H T C O 0 0 0 0 0 0 M S T A Y 0 0 1 A 3 0 X T A 0 0 1 A 5 0 S I 0 0 0 0 0 0 K M A Y 0 0 0 3 Delete the point removed from the loop Set_Up_Loop_Points option 5 4 Insert the new element having previously made note of the point number 5 Search loop element Set_Up_Loop_Points option 2 When this has been completed the configuration will be shown on the ...

Page 95: ...____________________________________ __________________________________________________________________ __________________________________________________________________ __________________________________________________________________ __________________________________________________________________ __________________________________________________________________ ____________________________...

Page 96: ...E PRODUCTOS CONTRA INCENDIOS FIRE PROTECTION MANUFACTURER FABRICANTS DE PRODUITS CONTRE INCENDIES C Compositor Wagner 8 P I Can Jardí 08191 RUBÍ Barcelona SPAIN Tlf 34 935 862 690 cofem cofem com www cofem com 1973 ...