TECHNICAL CHARACTERISTICS
FRONT PANEL
* The system has 10 A delayed fuses for the auxiliary pumps, a fuse of 20 A for the INVERTER an another one of 20 A for the
general supply. In case of pumps with another consumption, the suitable fuses should be chosen.
(Fig.9)
1- LCD screen. Shows the pressure in working mode.
2- MANUAL START-STOP pushbuttons, they are operative only with AUTOMATIC mode disabled
(green led (4) off).
3- Pushbutton AUTOMATIC (ON/OFF).
ON: green led bright.
OFF: green led dull (in this case, AUTOMATIC mode is enabled).
4- Green led light for MANUAL/AUTOMATIC mode.
5- With this pushbutton we can exit or enter MENU.
6- With these pushbuttons we can change programming values showed in the LCD screen (1).
7- ENTER for saving programmed values. Every pulsation is succeeded by a new field of the
CONFIGURATION MENU. Whenever we want to quit the configuration sequence press MENU (5).
8- Led lights:
• LINE green:Electric supply. ON when it is connected.
• FAILURE red: Bright or intermittent depending on type of failure.
• ON P1 yellow: Pump 1 ON.
• ON P2 yellow: Pump 2 ON.
• ON P3 yellow: Pump 3 ON (only types 3010, 3110, 311110).
EN
2010/3010
2110/3110
21110/31110
Power supply voltage
~3x400 Vca ( 320÷440 V)
~1x230 Vca (160÷250 V) ~1x230 Vca (160÷250 V)
Frequency
50/60 Hz
50/60 Hz
50/60 Hz
Max. current pump 1
(main pump)
10 A*(~3x230 Vca en D)
10 A*(~3x230 Vca)
9 A*(~1x230 Vca)
Max. Current pump 2
(auxiliary)
5 A* (~3x400 Vca en Y)
10 A* (~1x230 Vca)
9 A* (~1x230 Vca)
Max. Current pump 3
(auxiliary)
5 A * (~3x400 Vca en Y)
10 A * (~1x230 Vca)
9 A * (~1x230 Vca)
Max. operating pressure
16 bar
16 bar
16 bar
Max. set pressure
0÷12 bar
0÷12 bar
0÷12 bar
Protection index
IP55
IP55
IP55
Max. water temperature
40ºC
40ºC
40ºC
Max. environment temp.
0-50ºC
0-50ºC
0-50ºC
Max. flow
15.000 l/h
15.000 l/h
15.000 l/h
Fig. 9