10. CONFIGURATION.
In the configuration menu we can adjust either maximum current (A) and minimum pump speed (FL).
Next steps shoud be followed:
1. Press push-button
MENU
during 3 seconds to start the configuration se
-
quence.
2. Set the nominal current of the pump in Amps using
↑↓
enabling the ther
-
mal protection.
For the device must be within 0 and 7.5 A.
This value is located over the characteristics plate of the motor. Press
ENTER
for validation.
3. Using
↑
can be increased the lower limit of the speed of rotation.
The value must be within 30 and 35 Hz. Default value is 30 Hz.
Press push-button
ENTER
, for validation and quit this menu.
4. System is ready. By mean of
AUTO ON/OFF
quit the manual operating
mode.
11. REGISTER OF OPERATION DATA AND ALARMS.
By using simultaneously
MENU + ↑
during 3” is acceded to register of operation data and alarms, by
mean of
ENTER
we can advance through the sequence, once finished the sequence we come back to the
main display. This is all the sequence:
REGISTER HOURS (HF).
Counter of total time that the device has been operating.
REGISTER PUMP HOURS (HP).
Counter of total time that the pump has been operating.
REGISTER STARTS (CF).
Number of cycles of operation, a cycle is a start and a stop.
REGISTER SWITCH (Cr).
Number of connections to the electric supply.
ALARM COUNT DRY RUN (A1).
Number of dry-running alarms.
ALARM COUNT I MAX (A2).
Number of overcurrent alarms.
ALARM COUNT. DISCONNECTED PUMP (A3).
Number of disconnected pump alarms.
ALARM COUNT. LEVEL (A4).
Not available on this model.
ALARM COUNT. PRESSURE SENSOR (A5).
Number of pressure sensor faults.
ALARM COUNT. TEMP (A6).
Number of alarms by excessive temperature.
ALARM COUNT. SHORTCIRCUIT (A7).
Number of short circuit alarms.
ALARM COUNT. OVERVOLTAGE (A8).
Number of overvoltage alarms.
ALARM COUNT. UNDERVOLTAGE (A9).
Number of undervoltage alarms.
All the records are saved even if the device has been disconnected from the electric supply.
Note: For quantities with more than 2 figures they will appear in consecutive screens after each ENTER. For
example, to indicate 10234 overcurrent alarms: