ADVANCED MENU
+ +
- Press simultaneously + +
during 5 seconds.
- By mean of or the values can be changed.
- Press for validation.
- The parameters sequence is:
TYPE
SYSTEM REACTION
FACTORY
SETTING
Ar0
Ar1
Activation of the automatic restore
system ART (Ar1) o disable (Ar0).
Ar1
n01
n48
In case of enabled ART, it can be
set the number of restore at-
tempts, between 1 and 48.
48
t10
t40
It can be set the span of the at-
tempt between 10 and 40 seconds.
15”
Sb0 Sb1
Stand-by disabled (Sb0) or
enabled (Sb1)
0
rs0
rs1
Restore factory settings (rs1)
rs0
PF0 PF1
With PF1 is activated the pressure
dependent mode with start and
stop pressures.
0
P0.0 P_ON
With P_ON is activated a mini-
mUM working pressure. Under
this pressure is activated an alarm
(A11).
0.0
t05
t99
Time, in seconds, under minimal
pressure necessary to activate A11.
05
rs0
rs1
Restore factory settings (rs1)
rs0
PRESSURE SENSOR CALIBRATION
In case of wrong lecture of the pressure sensor it can be
adjusted again.
For the pressure sensor calibration is necessary to have a
pressure gauge in the installation. Proceed following next
steps:
ZERO REGULATION
1. Open the taps living the hydraulic net without pressure.
2. Press simultaneously the buttons and until the
display show 0.0 flashing.
3. Press to validate.
FULL SCALE
1. Start the pump until cut-out of the pressure switch.
2. Press simultaneously the buttons and till the dis-
play flashes with a figure.
3. Adjust the pressure with the arrows push-buttons to get
the pressure desired.
4. Press to validate.
Remark: pressure sensor decalibration should not be
a normal event. If it is frequently repeated contact the
technical service.
WARNINGS AND ALARMS
COD. ALARM DESCRIPTION
SYSTEM REACTION
A01
O
DRY RUNNING
When is detected a dry-
run operation the pump is
automatically stopped. By
mean of ENTER the normal
operation can be manually
restored.
( ( O ) )
After the activation of the
dry-running alarm if the
Automatic system reset
(ART) is enabled, a first
attempt at 5 minutes and
then an attempt every 30
minutes for 24 hours is
performed in order to res-
tore the normal operation.
This alarm can also be reset
manually with the ENTER
push-button. If the alarm
persists after 24 h we find a
definitive alarm.
A11
( ( O ) )
MINIMUM
PRESSURE
It detects pressure be-
low a pre-set value and
for a pre-set period in the
ADVANCED PROGRAM-
MING MENU. The minimum
pressure helps to detect
a dry-run operation or
pumps running far from its
best efficiency point. This
alarm is reset automatically
as soon as the pressure
exceeds the limit value.
A02
O
OVERLOAD
Overcurrent alarm is acti-
vated when the nominal
pump current is exceeded.
4 automatic reset attempts
prior to the final alarm are
performed.
Normal operation can also
be restored manually by
pressing ENTER.
( ( O ) )
A05
O
DAMAGED
PRESSURE
TRANSMITTER
CONTACT WITH YOUR
SUPPLIER