Technical Manual
CODEL
33
Note that this is Standard Modbus protocol NOT Modbus Plus protocol. Reference: AEG Modicon
Modbus Protocol Reference Guide PI-MBUS-300 Rev.D.
0070h
NO ppm data 0001h = 1ppm, 001Eh = 30ppm
0071h
CO ppm data 0001h = 1ppm, 0190h = 400ppm
0072h
Opacity data 0001h = 0.01%, 0064h = 1.00%
0073h
MOR data 0001h = 1m, 03E8h = 1000m
0074h
Vis dim coeff data 0001h = 0.0001m-1, 00AAh = 0.0170m-1
0075h
Optical transmission data 0001h = 0.01%, 0064h = 1.00%
0076h
NO/CO detector validation data 0000h = valid,>0000h = invalid
xx01h CO D1 value too large
xx02h CO D2 value too large
xx04h CO D1 value too small
xx08h CO D2 value too small
xx10h CO D1 or D2 in saturation
01xxh NO D1 value too large
02xxh NO D2 value too large
04xxh NO D1 value too small
08xxh NO D2 value too small
10xxh NO D1 or D2 in saturation
0077h
Vis emitter low/calibration data 0000h = valid, >0000h = invalid
xx01h Tunnel wash calibration (takes 30 minutes)
xx02h Power-up calibration (takes 4 hours)
01xxh Vis emitter too low
0078h
CO detector validation/calibration data 0000h = valid, >0000h = invalid
Joint version of 0076 & 0077 (CO flags in high byte)
007Eh
Head type identifier xx01h = AQM
1) Each register is defined to be 2 bytes wide.
2) 30ppm will be represented by binary 0000000 00011110 = 001Eh (hexadecimal).
3) CRC 16 is implemented.
4) Each AQM will have address switch SW1 set as required for the MODBUS address.
Modbus
register
location
Summary of Contents for Tunnel Tech 700 Series
Page 2: ...Issue A Rev 0 Date 25 04 17 Ref 100303...
Page 3: ...CODEL Issue A Rev 0 Date 25 04 17 Ref 100303...
Page 5: ...CODEL Issue A Rev 0 Date 25 04 17 Ref 100303...
Page 6: ......
Page 10: ...Technical Manual CODEL Issue A Rev 0 Date 25 04 17 Ref 100303...
Page 21: ...Technical Manual CODEL 11 Figure 7 Electrical Schematic...
Page 23: ...Technical Manual CODEL 13 Power Control Display PCB Electrochemical Cell PCB Communications...
Page 24: ...Technical Manual CODEL 14 Visibility PCB Ma Output PCB S Top mA RLY 4 5 Bottom mA RLY 1 2...
Page 37: ...Technical Manual CODEL 27 Alignment Laser Please Call CODEL mA Relay Card 803 604D...
Page 79: ......
Page 80: ......
Page 81: ...Technical Manual Page 1 CODEL...