Standard MODBUS Communication with CODEL MODBUS TT AQM
Summary
Using standard MODBUS protocol function 03 allows a host to obtain the contents of one or more
holding registers in the CODEL MODBUS TT Air Quality Monitor (AQM). The request frame from the
host (typically a DCS or SCADA) defines the relative address of the first holding register followed by
the total number of consecutive registers to be read.
The response frame from the CODEL TT AQM lists the contents of the requested registers, returning
2 bytes per register with the most significant byte first. A maximum of 125 registers can be accessed
per request. The formats of the request and response frames are detailed below, where ‘X’ and ‘n’ are
hexadecimal variables. An example of a MODBUS register map is shown below.
Host Request Frame
01
Address
03
Function code
XX
XX
Address of starting register
00
XX
Number of consecutive
registers to be read
XX
XX
CRC
Slave Response (from CODEL MODBUS TT AQM)
01
Address
03
Function code
XX
Byte count
XX
XX
…to… …to…
Date from starting register
XX
XX
Date from nth register
XX
XX
CRC
Standard baud rate
-
4800
Bits per byte
-
1 start bit
-
8 data bits (least significant sent first)
-
1 stop bit
-
no parity
The MODBUS output from the TT AQM is at 4800 baud format: 1 start bit, 8 data bits, no parity, 1
stop bit.
The MODBUS output from the TT AQM will be connected via RS485.
The TT AQM comms is Standard Modbus protocol with RTU framing and only function code 03 is
supported.
The TT AQM will be a MODBUS slave device.
Summary of Contents for Tunnel Tech 700 Series
Page 2: ...Issue A Rev 0 Date 25 04 17 Ref 100303...
Page 3: ...CODEL Issue A Rev 0 Date 25 04 17 Ref 100303...
Page 5: ...CODEL Issue A Rev 0 Date 25 04 17 Ref 100303...
Page 6: ......
Page 10: ...Technical Manual CODEL Issue A Rev 0 Date 25 04 17 Ref 100303...
Page 21: ...Technical Manual CODEL 11 Figure 7 Electrical Schematic...
Page 23: ...Technical Manual CODEL 13 Power Control Display PCB Electrochemical Cell PCB Communications...
Page 24: ...Technical Manual CODEL 14 Visibility PCB Ma Output PCB S Top mA RLY 4 5 Bottom mA RLY 1 2...
Page 37: ...Technical Manual CODEL 27 Alignment Laser Please Call CODEL mA Relay Card 803 604D...
Page 79: ......
Page 80: ......
Page 81: ...Technical Manual Page 1 CODEL...