SIZE
Sound power level (dB) - Octave band (Hz)
Sound
pressure
level
Sound
power
level
63
125
250
500
1000
2000
4000
8000
dB(A)
dB(A)
80.3
58
71
75
79
79
80
71
64
65
84
100.4
59
72
77
80
78
80
72
66
65
84
115.4
60
73
78
81
81
82
73
66
66
86
130.4
59
72
77
81
81
82
73
65
66
86
155.5
59
71
76
80
82
81
73
65
66
86
170.5
60
71
77
81
83
82
74
66
67
87
185.5
60
72
77
82
84
83
75
66
68
88
210.6
61
72
78
82
84
83
75
66
67
88
225.6
61
72
77
82
84
84
75
66
67
88
240.6
61
72
78
83
85
84
76
66
68
89
Sound levels refer to full load units, in test nominal conditions. The sound pressure level refers to 1 m. from the standard unit outer surface operating in open field. Measures accor-
ding to UNI EN ISO 9614-2 regulations, with respect to the EUROVENT 8/1 certification, which provides for a tolerance of 3 dB(A).
Data referred to the following conditions:
- internal exchanger water temperature = 12/7 °C
- ambient temperature = 35 °C
Super-silenced acoustic configuration (EN)
66
Summary of Contents for WSAT-YSC4
Page 1: ...R32 M0T400002 01 09 21 MANUAL FOR INSTALLATION USE AND MAINTENANCE...
Page 2: ......
Page 3: ......
Page 19: ...Connections performed by costumer 5 ELECTRICAL CONNECTIONS...
Page 37: ...7 CONTROL...
Page 39: ...7 CONTROL...
Page 40: ...7 CONTROL...
Page 55: ...10 ANTIVIBRATION MOUNTS 1 2 3 4 5 7 6 8...