SIZE
90.3
110.4
130.4
145.4
170.5
185.5
210.6
225.6
240.6
Compressor
Type of compressors
1
SCROLL
Refrigerant
R-32
No. of compressors
Nr
3
4
4
4
5
5
6
6
6
Rated power (C1)
HP
25
50
65
65
50
65
105
105
120
Rated power (C2)
HP
65
60
65
80
120
120
105
120
120
Std Capacity control steps
4
6
6
6
5
7
8
8
6
Oil charge (C1)
l
4
9
11
11
9
11
17
17
23
Oil charge(C2)
l
11
11
11
13
23
23
17
23
23
Refrigerant charge (C1)
kg
10
15
16
17
19
19
24
28
29
Refrigerant charge (C2)
kg
22
14
15
18
25
25
25
26
30
Refrigeration circuits
Nr
2
2
2
2
2
2
2
2
2
Internal exchanger (evaporator)
Type of internal exchanger
2
PHE
N. of internal exchanger
Nr
1
1
1
1
1
1
1
1
1
Water content
l
20
20
24
28
36
48
48
57
60
Minimum system water content
l
2350
2050
2550
2350
2800
2950
3250
3550
5450
External exchanger (condenser)
Type of external exchanger
3
CCM
Number of coils
Nr
3
4
4
5
6
6
7
8
8
External Section Fans
Type of fans
4
AX
Number of fans
Nr
3
4
4
5
6
6
7
8
8
Type of motor
5
EC
Standard airflow (ST/SC)
l/s
16333
21778
21778
27222
32667
32667
38111
43556
43556
Standard airflow (EN)
l/s
13750
18333
18333
22917
27500
27500
32083
36667
36667
Connections
Water fittings
4"
4"
4
4"
5"
5"
5"
5"
5"
Power supply
Standard power supply
400/3~/50
Electrical data
F.L.A. - Total
A
171,1
209,7
246,7
276,5
324,2
352,1
399,9
429,7
457,5
F.L.I. - Total
kW
105,0
128,2
152,2
171,9
200,7
219,1
248,0
267,6
286,0
M.I.C. - Value
6
A
505,4
544,0
581,0
610,8
658,6
686,4
734,2
764,0
791,8
M.I.C. - with soft start accessory
6
A
327,4
366,0
403,0
432,8
480,6
508,4
556,2
586,0
613,8
1. ISW = Double screw compressor
2. S&T = Shell and tube
3. CCM = Full aluminium microchannel coils
4. AX = Axial fan
5. EC = Asynchronous motor with permanent magnet commuted electronically.
6. M.I.C.=Maximum unit starting current. The M.I.C. value is obtained adding the max. compressor starting current of the highest size to the power input at max. admissible condi-
tions (F.L.A.) of the remaining electric components.
Unbalance between phase max 2 %
Voltage variation: max +/- 10%
Electrical data refer to standard units; according to the installed accessories, the data can suffer some variations.
Construction
Premium
64
Summary of Contents for WSAT-YSC4
Page 1: ...R32 M0T400002 01 09 21 MANUAL FOR INSTALLATION USE AND MAINTENANCE...
Page 2: ......
Page 3: ......
Page 19: ...Connections performed by costumer 5 ELECTRICAL CONNECTIONS...
Page 37: ...7 CONTROL...
Page 39: ...7 CONTROL...
Page 40: ...7 CONTROL...
Page 55: ...10 ANTIVIBRATION MOUNTS 1 2 3 4 5 7 6 8...