Start-up sequence
Unit power supply ON
Before powering the unit carry out a leak test with suitable instrumentation
6 - START-UP
Yes / No
1 compressor carter resistances operating at least since 8 hours
2 off-load voltage measure
3 phase sequence check
4 pump manual start-up and flow check
5 refrigeration circuit shut-off valves opening (if applicable)
6 unit ON
7 load voltage measure
8 verify the lack of bubbles in the liquid light (if applicable)
9 check of all fan operating: no abnormal noises or vibrations
10 measure of return and supply water temperature
11 super-heating and sub-cooling measure
12
run tests in both heat and cool mode (only for heat pump units)
13 check no anomalous vibrations are present
14 set-point personalization
15 scheduling customisation
16
check that all panels are closed and fastened properly
17 complete and available unit documentation