8
Operate in compliance with safety regulations in force.
For detailed information (dimensions, weight, technical
characteristics etc.) please refer to the TECHNICAL
INFORMATION section.
Use single protection devices : gloves, glasses ecc.
During positioning consider these elements :
technical spaces required for the machine and system
place where the machine will be installed
electrical connections
water connections
air / aeraulic ducts
Do not considerer these elements could decrease
performances and operational life of the unit.
3.1 PRELIMINARY INFORMATION
leaves or other foreign bodies that can obstruct the
exchange batteries;
winds that hinder or favour the airflow;
heat or pollution sources close to the unit (chimneys,
extractors etc);
stratification (cold air that stagnates at the bottom);
recirculation (expelled air that is sucked in again);
positioning below the level of the threshold, close to very
high walls, attics or in angles that could give rise to
stratification or recirculation phenomenons.
Ignoring the previous indications could:
energy efficiency decrease;
blocks due to HIGH PRESSURE (in summer) or LOW
PRESSURE (in winter).
3.4 FRESH AIR PROBE
The external probe allows to automatically change the unit
setpoint according to the external enthalpy (tempe
humidity).
In this way is not possible to optimize the unit energy
efficiency .
In the winter operating also the defrosting times are optimized.
POSITIONING
The sensor must not be influenced by factors that can cause a
false reading (for example direct sun rays, air expelled by the
fan or other sources, contact with the unit structure or other
heat sources, accumulation of snow/ice).
Example for the positioning of the external probe:
A attic
B Underneath a terrace
C If attached to external wall provide a small roof
framework
3.2 FUNCTIONAL SPACES
3.3 POSITIONING
Functional spaces are designed to:
guarantee good unit operation
Carry out maintenance operations
protect authorized operators and exposed people
Respect all functional spaces indicated in the TECHNICAL
INFORMATION section.
Double all functional spaces if two or more unit are aligned.
Units are designed to be installed:
EXTERNAL
in fixed positions.
Limit vibration transmission:
use antivibration devices on unit bearing/supporting
points;
install flexible joints on the hydraulic.
Installation standards:
Safe accessible position;
avoid flood-prone places;
verify unit weight and bearing point capacity;
verify that all bearing points are aligned and leveled;
install the unit raised from the ground;
consider the maximum possible snow level
A correct circulation of the air is indispensible to guarantee the
good working order of the machine.
Avoid therefore:
obstacles to the airflow;
exchange difficulties;
3 - POSITIONING
Summary of Contents for WSAT-XEE 352
Page 66: ...Page intentionally left blank 66...
Page 67: ...Page intentionally left blank...