Excellence version (EN)
General technical data (EN)
Acoustic Treatment: extremely low noise (EN)
Size
352
402
432
452
502
552
602
702
802
Cooling
Cooling capacity
1
kW
91,5
104
116
125
134
145
165
185
207
Compressor power input
1
kW
28,5
32,9
37,1
37,7
42,1
46,1
53,4
58,5
66,2
Total power input
2
kW
30,1
34,5
38,7
39,9
44,3
48,3
55,6
61,4
69,1
Total recovery heating capacity
3
kW
119
139
151
161
176
190
215
242
269
Partial recovery heating capacity
3
kW
30,0
34,2
38,2
40,6
44,2
48,0
55,1
60,8
68,8
EER
1
3,04
3,01
2,99
3,13
3,03
3,01
2,96
3,01
3,00
Cooling capacity (EN14511:2013)
4
kW
91,0
103
115
124
134
145
164
184
206
Total power input (EN14511:2013)
4
kW
30,6
35,2
39,3
40.6
44,9
48,9
56,4
62,0
69,9
EER (EN 14511:2013)
4
2,97
2,94
2,93
3,06
2,98
2,96
2,91
2,97
2,95
ESEER
4
4,08
4,22
4,15
4,14
4,12
4,10
4,09
4,15
3,98
Compressor
Type of compressors
SCROLL
SCROLL
SCROLL
SCROLL
SCROLL
SCROLL
SCROLL
SCROLL
SCROLL
No. of compressors
No
2
2
2
2
2
2
2
2
2
Rated power (C1)
HP
35
40
43
45
50
55
60
70
80
Std Capacity control steps
No
3
3
3
3
3
3
2
3
2
Oil charge (C1)
l
8,00
10,0
12,0
10,0
11,0
13,0
13,0
13,0
13,0
Refrigerant charge (C1)
5
kg
28,3
28,3
31,9
39,5
39,5
39,5
44,6
51,3
57,9
Refrigeration circuits
No
1
1
1
1
1
1
1
1
1
Internal exchanger
Type of internal exchanger
6
PHE
PHE
PHE
PHE
PHE
PHE
PHE
PHE
PHE
Water flow rate (Utility Side)
1
l/s
4,40
5,00
5,50
6,00
6,40
6,90
7,90
8,80
9,90
Internal exchanger pressure drops
1
kPa
26,8
26,9
28,0
32,1
30,8
35,1
37,3
36.3
38.1
Water content
l
6.90
8.00
8.90
8.90
10.1
10.1
11.9
14.2
17.2
External Section Fans
Type of fans
7
AX
AX
AX
AX
AX
AX
AX
AX
AX
Number of fans
No
2
2
2
3
3
3
3
4
4
Standard air flow
l/s
9636
9571
9517
14358
14358
14253
14138
18925
18798
Connections
Water connections
2” 1/2
2” 1/2
2” 1/2
2” 1/2
2” 1/2
2” 1/2
2” 1/2
2” 1/2
2” 1/2
Power supply
Standard power supply
V
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
Dimensions
A - Length
mm
3075
3075
3075
4025
4025
4025
4025
5025
5025
B - Width
mm
1097
1097
1097
1097
1097
1097
1097
1097
1097
C - Height
mm
1805
1805
1805
1805
1805
1805
1805
1805
1805
Standard unit weights
Shipping weight
kg
889
925
1015
1198
1224
1246
1290
1483
1527
Operating weight
kg
896
933
1024
1207
1234
1256
1302
1497
1544
1. Data referred to the following conditions: internal exchanger water = 12/7 °C external exchanger inlet air 35°C
2. The Total Power Input value does not take into account the part related to the pumps and required to overcome the pressure drops
for the circulation of the solution inside the exchangers
3. Option. Recovery exchanger water = 40/45°C
4. Data calculated in compliance with Standard EN 14511:2013 referred to the following conditions: Internal exchanger water
temperature = 12/7°C. External exchanger intake air temperature = 35°C
5. indicative values for standard units with po/-10% variation. The actual data are indicated on the label of the unit.
6. PHE = plates
7. AX = axial fan