7 - CONTROL
ALARMS - TAB 1
code
description
description
t.i.
module
input
t.a
.
eE001
phase monitor
Phase monitor
DI
687 central
T13 DL1
A/M
EE003
pump 1 faulty
Pump 1 faulty
DI
687 central
T13 DL2
M
EE004
pump 2 faulty
Pump 2 faulty
DI
687 central
T4 D1
M
EE005
pump 3 faulty
Pump 3 faulty
DI
687 central
T13 DL2
M
ee010
master offline
Master Offline - Master Slave network enabled
A
ee011
unit 2 in alarm
Unit 2 in alarm - Master Slave network enabled
A
ee012
unit 2 offline
Unit 2 OffLine - Master Slave network enabled
A
ee013
unit 3 in alarm
Unit 3 in alarm - Master Slave network enabled
A
ee014
unit 3 offline
Unit 3 OffLine - Master Slave network enabled
A
ee015
unit 4 in alarm
Unit 4 in alarm - Master Slave network enabled
A
ee016
unit 4 offline
Unit 4 OffLine - Master Slave network enabled
A
ee017
unit 5 in alarm
Unit 5 in alarm - Master Slave network enabled
A
ee018
unit 5 offline
Unit 5 OffLine - Master Slave network enabled
A
ee019
unit 6 in alarm
Unit 6 in alarm - Master Slave network enabled
A
ee020
unit 6 offline
Unit 6 OffLine - Master Slave network enabled
A
ee021
unit 7 in alarm
Unit 7 in alarm - Master Slave network enabled
A
ee022
unit 7 offline
Unit 7 OffLine - Master Slave network enabled
A
EE023
Pump 1 overload
Pump 1 thermal protection
DI
965 hydronic
T1 X4
M
EE024
Pump 2 overload
Pump 2 thermal protection
DI
965 hydronic
T1 X5
M
The alarm code identifies the concerned circuit:
Es:
ee
1
01 :TimeOutModCirc = circuit 1
ee
2
01 :TimeOutModCirc = circuit 2
The number of refrigerant circuits depends on series and size
of the unit.
t.i. input type:
DI digital input
AI analogic input
module:
687 = main module
985 = circuit module
94U = thermostatic driver module
input:
connector number: T1, T2, T3...
PIN code: X1, X2, Q13, DO1....
t.a. alarm type:
A automatic reset
M manual reset
A/M rautomatic reset , after N alarm → manual reset