7 - CONTROL
GENERAL STATA E CENTRAL MODULE
code
description
description
AI-687
Temp.In H2O
userside_B1
Inlet water temperature utility side
AI-687
Temp.Out H2O
userside_B1
Outlet water temperature utility side
AI-687
Ext.Air temp_B3
External air temperature
AI-687
S.DemandLimit_X1
Demand limit signal
AI-687
S.WaterReset_X2
Water reset signal
AI-687
RHExt_X3
External humidity
AI-687
El.CabinetTemp_X4
Cabinet temperature
AO-687
%FreeCooling _X5
% value external freecooling signal
DI-687
Sel.SetPoint_DU2
2nd setpoin status : 0=1°set 1=2°Set
DI-687
SystemPressure_DU1
System pressure probe status: 0=OK 1=Fault
DI-687
FlowUser_X8
Flow switch utility side status: 0=OK 1=Fault
DI-687
RemON-OFF_X7
Unit status: 0=OFF 1=On
DI-687
Heat/CoolRem_X6
Unit mode: 0=Heat 1=Cool
DI-687
PhaseMonitor_DL1
Phase monitor : 0=OK 1=Fault
DI-687
OvlP1Util_D2
Pump1 thermal protection utility side: 0=OK 1=Fault
DI-687
OvlP2Util_D1
Pump2 thermal protection utility side: 0=OK 1=Fault
DI-687
OvlP3Util_DL2
Pump3 thermal protection utility side: 0=OK 1=Fault
DO-687
El.CabinetFAN_DO1
Cabinet fan : 0=Off 1=On
DO-687
El.CabinetHEAT_DO2
Cabinet heating : 0=Off 1=On
DO-687
UnitMode_Q1
Unit mode digital output (N.O. open=Cool N.O. closed=Heat):
0=Cool 1=Heat
DO-687
Cumul.Alarm_Q2
Cumulative alarm (N.O. open=All OFF N.O. closed=All ON): 0=Off 1=On
DO-687
CmdP1User_Q3
Command pump 1 utility side : 0=Off 1=On
DO-687
CmdP2User_Q4
Command pump 2 utility side : 0=Off 1=On
DO-687
CmdP3User_Q5
Command pump 3 utility side : 0=Off 1=On
DO-687
OpenYV FC_Q7
Free-cooling opening command closed FC = ON: 0=Off 1=On
DO-687
CloseYV FC_Q8
Free-cooling closing command closed FC = OFF: 0=Off 1=On
DO-687
AntifreezeHeater_Q6
Antifreeze heater : 0=Off 1=On
S0001
StartsP1User
Starts pump1 utility side
S0002
StartsP2User
Starts pump2 utility side
S0003
StartsP3User
Starts pump3 utility side
S0004
Pump1 running hours
Hours pump1 utility side
S0005
Pump2 running hours
Hours pump2 utility side
S0006
Pump3 running hours
Hours pump3 utility side
S0007
Antifreeze heat.
Antifreeze heater 0=Off 1=On
S0008
pump in antifreeze
alarm
Pump ON by antifreeze alarm: 0=Off 1=On
S0009
recovery
Recovery 0=Off 1=On
S0010
ActualSptText
Actual setpoint by external temperature
S0011
ActualSptWR
Actual setpoint by Water Reset
S0012
StatusFreeCooling
FreeCooling 0=Off 1=On
S0013
GenWarning
0=Off 1=On
S0014
GenBlock
0=Off 1=On
S0015
NCompOnUnit
Active compressors