Dimensional drawings: Excellence version
WSAT-XEE 352-402-432
1. Internal exchanger (evaporator)
2. External exchanger (condenser)
3. Unit fixing holes
4. Lifting brackets (removable, if required, after the unit positioning)
5. Electrical panel
6. Power input
7. Soundproofed cabin
8. Internal exchanger water outlet. The heights of the connections may change if
there are optional components: pump, storage tank, free-cooling, partial or total
recovery.
9. Internal exchanger water inlet. The heights of the connections may change if
there are optional components: pump, storage tank, free-cooling, partial or total
recovery.
10. Minimum Safe Clearance
11. Minimum Clearance for a Proper Air flow to the Condenser
12. Minimum Clearance Electrical Panel Side
(G) Centre of gravity
SC-EXC
EN-EXC
Size
352
402
432
352
402
432
M
mm
1933
1946
2011
1933
1946
2011
N
mm
1142
1129
1064
1142
1129
1064
O
mm
579
581
590
579
581
590
P
mm
518
516
507
518
516
507
OD
mm
76
76
76
76
76
76
Length
mm
3075
3075
3075
3075
3075
3075
Depth
mm
1097
1097
1097
1097
1097
1097
Height
mm
1805
1805
1805
1805
1805
1805
W1 Supporting Point
kg
149
153
156
149
153
156
W2 Supporting Point
kg
325
342
396
325
342
396
W3 Supporting Point
kg
161
165
168
161
165
168
W4 Supporting Point
kg
261
272
304
261
272
304
Shipping weight
kg
889
925
1015
889
925
1015
Operating weight
kg
896
933
1024
896
933
1024
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
60
Summary of Contents for WSAT-XEE 352
Page 66: ...Page intentionally left blank 66...