![CLIVET WSAR-MT-E Installation, Use And Maintenance Manual Download Page 66](http://html1.mh-extra.com/html/clivet/wsar-mt-e/wsar-mt-e_installation-use-and-maintenance-manual_2625598066.webp)
66
9.2 TECHNICAL DATA : BASE configuration
9 - TECHNICAL INFORMATION
SIZE
21 25 31 41 51 61 81
Type of internal compressor
SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL SCROLL
No. of internal compressor
Nr
1
1
1
1
1
1
1
Refrigerant charge (R407C)
7
kg
3.1 5.8 5.8 5.8 6.2 7.5 8.0
Std Capacity control steps
Nr
1
1
1
1
1
1
1
Refrigerant
circuits
Nr
1 1 1 1 1 1 1
COMPRESSOR
Type of internal exchanger
8
PHE PHE PHE PHE PHE PHE PHE
No. of internal exchangers
Nr
1
1
1
1
1
1
1
Water flow rate
1
l/s
0.29
0.39
0.48
0.54
0.67
0.85
1.09
Exchanger pressure drops
1
kPa
18
19
20
23
23
20
25
Water
content
l 0.5 0.6 0.7 0.7 0.8 1.1 1.4
INTERNAL EXCHANGER
Type of fans
9
AX
AX
AX
AX
AX
AX
AX
Number
of
fans
Nr
1 1 1 1 1 1 1
Standard air flow
m
3
/h
2500 2800 3200 3400 3400 7000 8000
FANS
Sound pressure level (10m)
6 dB(A)
31
33
35
36
37
43
44
Max water side pressure
kPa 270 270 270 270 270 270 270
Safety valve calibration
kPa 300 300 300 300 300 300 300
Water fittings
1” 1” 1” 1” 1”
1
¼”
1¼”
HYDRAULIC CIRCUIT
Length
mm
1370 1370 1370 1370 1370 1625 1625
Depth
mm
800 800 800 800 800 1250 1250
Height
mm
1515 1515 1515 1515 1515 1765 1765
Unit packing volume
m
3
1.67 1.67 1.67 1.67 1.67 2.12 2.12
Casing packing volume
m
3
1.08 1.08 1.08 1.08 1.08 1.37 1.37
Unit / panels / hoods shipping weight
kg
108/37/50 108/37/50 113/37/50 113/37/50 133/37/50 195/55/75 255/55/75
Operating
weight
kg
195 205 210 210 235 315 375
DIMENSIONS
/
STANDARD UNIT WEIGHTS
HEATING A7(6)W30/35
Heat output
1
kW
6.13 8.16 10.0 11.2 14.0 17.7 22.9
Total power input
1
kW
1.57 2.05 2.51 2.87 3.55 4.42 5.87
COP
EUROVENT
4
3.95 4.03 4.03 3.96 4.00 4.06 3.96
COP
EN14511
3.91 3.98 3.98 3.90 3.94 4.01 3.90
COP
EN14511
(with high efficiency option only in heating)
4.10 4.12 4.10 4.16 4.11 4.14 4.10
COOLING A35W23/18
Cooling capacity
3
kW
6.44 8.50 10.7 11.9 14.5 18.1 22.4
Total power input
3
kW
2.26 2.99 3.81 4.46 5.61 6.26 8.07
EER
EUROVENT
4
2.88 2.87 2.83 2.68 2.61 2.92 2.81
230/1/50
Heat output
1
kW
6.22 7.91 10.2 11.3 - - -
Total power input
1
kW
1.69 2.03 2.73 3.01 - - -
COP
EUROVENT
4 kW
3.72 3.94 3.78 3.80 - - -
COP
EN14511
(with high efficiency option only in heating)
4.10 4.14 4.11 4.12 -
-
-
COP
EN14511
3.69 3.90 3.73 3.75 - - -
COOLING A35W23/18
Cooling capacity
3
kW
6.46 8.03 10.3 11.9 - - -
Total power input
3
kW
2.47 3.15 4.11 4.76 - - -
EER
EUROVENT
4
2.64 2.57 2.52 2.52 - - -
Heat output
2
kW
4.81 6.49 7.83 8.80 11.1 13.9 18.1
Total power input
2
kW
1.49 1.92 2.35 2.72 3.33 4.11 5.48
COP
EN14511
3.24 3.38 3.33 3.24 3.34 3.38 3.31
400/3/50+N
HEATING A2(1)W30/35
HEATING A7(6)W30/35
HEATING A2(1)W30/35
Heat output
2
kW
4.92 6.25 8.01 8.91 - - -
Total power input
2
kW
1.59 1.90 2.54 2.83 - - -
COP
EN14511
3.10 3.29 3.15 3.14 - - -
ESEER 5
2.38 2.49 2.41 2.47 -
-
-
ESEER 5
2.62
2.62
2.71
2.57 2.46 2.74 2.51
NOISE LEVELS
All of the above data are compliant with standard EN 14511-1:2008 unless otherwise
specified.
Defrost cycles have already been taken into consideration.
Performance refers to a unit operating in optimal conditions of installation with the heat
exchangers perfectly clean.