7 - REGULATION
UNIT PARAMETER
tab 5
530
TStartPump
Pump starting time in maintenance
531
DlyPumpC
Pump shutdown delay from comp OFF
532
MaxTempC
Threshold of COOLING flow rate reduction
533
MinTempH
Threshold of HEATING flow rate reduction
534
IstTempC
Hysteresis of cooling flow rate reduction
535 IstTempH
Hysteresis
of
heating flow rate reduction
536
MinSignal
Pump signal corresponding to the max. flow rate reduction
537
MaxSignal
Pump signal corresponding to the nominal flow rate
540
PumpPFCorr
Evaporator pump power factor correction 1=500ns
541
TPompaMax
Pump max. waiting time before signalling the flow rate alarm
558
PotRes
Capacity delivered by the integration resistances
559
LimText
Outdoor temperature limit at the compressor operating
560
Tregime
Resistance Timeout
561
MaxInteg
Max. analogical output value of the integration resistances when they are activated at the same time
of the compressor
562
MinInteg
Min. analogical output value of the integration resistances in modulation phase
563
OffsetOnAux
Offset on the aux. insertion step
564
TextOnAux
Outdoor temperature limit at the auxiliary operating
579
TimeOutCModeI
Output time from the automatic control of the system temperature
580
TimeOutCModeS
Output time from the automatic control of the DHW temperature
581
TLimiteCool
Input water temp.: under it the activation of the compressor in COOL is allowed
582
TLimiteHeat
Input water temp.: over it the activation of the compressor in HEAT is allowed
598
OffsetBT1
Evaporator input temp. offset
599
OffsetBT2
Evaporator output temp. offset
600
OffsetBT4
Coil 1 temp. offset
601
OffsetBT7
Electric heater output temp. offset
602
OffsetBWS
Water Reset Offset
603
OffsetBT3
Outdoor temp. offset
604
OffsetBP1
High pressure offset
605
OffsetURExt
Ext RH Offset
606
OffsetBDL
Demand Limit Offset
607
OffsetBQ
BQ analogical Offset
608 OffsetBA
609
OffsetBT5
Source input temp. offset
610
OffsetBT6
Storage temp. offset
611
OffsetBP2
Low pressure offset
612
OffsetBT8
Free input Offset
628
OffsetRuggiada
Offset to reach at the dew temperature for the setpoint calculation
629
MaxTempRuggiada Max. limit for the dew point