51
7 - REGULATION
UNIT PARAMETER
tab 1
2
CompAmb
Enables Tambient comp. 0=No 1=Cool 2=Heat 3=Always
3
ENCCar
Enables load compensation 0=No 1=Cool 2=Heat 3=Always
4
CompExt
Enables Toutside comp. 0=No 1=Cool 2=Heat 3=Always
5
WaterReset
Enables Water Reset 0=No 1=Cool 2=Heat 3=Always
6
CompDutyEn
Enables Duty compensation 0=No 1=Cool 2=Heat 3=Always
7
DemandLimitEn Demand Limit enabling 0=None 1=priority of aux. release 2=priority of compressor release 3 =
Current measure
8
CompONEN
Enables Duration comp. 0=No 1=Cool 2=Heat 3=Always
12
EnH2OSanitaria Enabling of DHW management 0=No DHW, 1=DHW and system without restrictions, 2=DHW and
system heat only, 3=DHW and system cool only, 4=DHW only mode
13
CaldaiaEn
Enables boiler fu Heat pump 0=No/1=Always2=disabled in DHW
16
EnUrExt
Enables ext. RH% probe 1=Yes/0=No
17 EnDTIncongruent
e
Enables inconsistent DeltaT for units reversal on the refrigerant circuit 1=Yes/0=No
18
EnPaux
Enabling of the aux. heater 0=No/1=Always2=disabled in DHW
19
ControlMode
Enables the temperature automatic control
20
PumpBord
Presence of second pump 0=Customer management 1=Single pump on the unit 2=Single
pump+reserve 3=Pump at variable flow-rate
24
ControlPump
Enables off control of the utility pump: 0=No 1=according to the ambient set 2=according to the storage
temperature
25
RemOnOffMode Configure DI inputs 1=On/Off, 0=thermal request from the ambient
62
MaxCAmbC
Max. correction value for ambient temperature,Summer
63
DeltaCambC
Band of ambient setpoint for Ambient Temp. correction. Summer
64
MaxCAmbH
Max. correction value for ambient temperature,Winter
65
DeltaCambH
Band of ambient setpoint for Ambient Temp. correction. Winter
66
PesoCorTamb
Weight of the ambient temperature correction
82
CompCarC
Max. Summer charge compensation
83
CompCarH
Max. Winter charge compensation
84
MediaDelta
Time for the average on (Ting. - Tout)
85
MinDeltaC
Summer temperature min. delta
86
MaxDeltaC
Summer temperature max. delta
87
MinDeltaH
Winter temperature min. delta
88
MaxDeltaH
Winter temperature max. delta
104
CextMaxC
Out. Temp. of Summer max. correction
105
CextMinC
Out. Temp. of Summer min. correction
106
CextMaxH
Out. Temp. of Winter max. correction
107
CextMinH
Out. Temp. of Winter min. correction
108
MaxCExtC
Summer max. correction value
109
MaxCExtH
Winter max. correction value
110
HExtMinC
Min. correction ext. enthalpy
111
HExtMaxC
Max. correction ext. enthalpy
127
MaxCWRH
Max. value of the Winter WR correction
128
SWRMAXH
Signal of Winter max. correction
129
SWRMinH
Signal of Winter min. correction
ID
Description Extended
description