3 - POSITIONING
3.5 OUTDOOR VERSION
Please respect the clearances.(
1
)
If possible, position the unit so that the electrical panel is not
facing the wall.
The walls reflect and amplify noise emitted from unit : avoid
placing it in the corners (
2
).
In winter, the exhaust air from the unit reaches temperatures
below 0 ° C, with outside temperature of +10 ° C.
Maintain safe distances to avoid formation of frost on rain
water drains (
3-A
) and pedestrian walkways (
4
).
Provide (
5
):
•
raised cement base (A)
•
gravel for frost protection (B)
•
gravel - crushed stone for exhaust air condensate
absorption ( C )
Dispose the condensate produced from unit in winter mode in
ducts (
5-D
) or wells (
6-E
) below the frost line ( 900 mm).
!
1,5 mt
3
1
4
2
!
!
1,5 mt
A
B
C
1000 mm
D
900 mm
A
5
B
C
1000 mm
E
900 mm
A
6