60
7 - REGULATION
num Description
E
lectrical
R
efrigerant
H
ydraulic
Reset
M
anual
A
utomatic
A
larm
P
realarm
E 00
Base keypad Timeout
E/F/I
A
A
E 01
Input temp. probe utility side
E
A
A
E 02
Supply temp. probe utility side
E
A
A
E 03
Outside temp. probe
E
A
A
E 04
Coil temp. probe
E
A
A
E 06
Temp. probe in accumulation
E
A
A
E 07
AUX. heater temp. probe (utility side)
E
A
A
E 08
Pressure 1 probe (HP)
E
A
A
E 09
Pressure 2 probe (LP)
E
A
A
E 10
Ext. RH% probe
E
A
A
E 11
Water Reset input
E
A
A
E 12
Demand Limit input
E
A
A
E 13
Phase monitor
E
A
A
F 01
High pressure (HP)
F
A/M
A
F 02
Low pressure (LP)
F
A/M
A
F 03
Compressor 1 overload (or softstater)
F
M
A
F 05
Prealarm HP1
F
A
P
F 06
Prealarm LP1
F
A
P
F 07
Fan overload
F
M
A
f/F 10
Max pressure ratio
F
A/M
P/A
f/F 11
Defrosting forcing for low pressure
F
A/M
P/A
I 01
Utility pump flow
I
A/M
A
I 03
Pump 1 overload (utility side)
I
M
A
I 04
Pump 2 overload (utility side)
I
M
A
I 05
Frost alarm (utility)
I
M
A
I 06
Frost alarm
I
M
A
I 07
AUX heater antifreeze
I
M
A
I 08
Water charge system (utility)
I
M
A
I 09
Incongruent T Delta
I
M
A
I 10
Thermal alarm on all pumps (utility side)
I
M
A
I 11
Antifreeze prealarm (utility)
I
A
P
I 12
Pump change (utility)
I
A
P
I 13
User input water temperature out of limit of the current operating
mode
I A
P
I 14
Dom. hot water incongruent thermostat
I
A
P
I 15
Ambient antifreeze alarm
I
A
A
LIST OF ALARMS