Single/multiple pump system
Set up the DIP S12-2 according to the type of system.
Single water pump
The retaining valve is not necessary with this configuration.
The pump control is only activated on the master unit
Multiple water pumps.
A retaining valve for each unit is necessary with this
configuration.
Pump control is activated on each unit.
Single water pumps.
dip S12-2 = OFF
Multiple water pumps.
dip S12-2 = ON
14 MODULAR CONFIGURATION UNITS