8 - CONTROL
USER menu - TEMPERATURE COMPENSATION
Press
or
to select:
COOL MODE
HEAT MODE
The water temperature is adjusted based on the outdoor
temperature T4.
COOLING
The following parameters can be adjusted:
T4_cool_1 (25~30ºC)
T4_cool_2 (30~40ºC)
offset_c (0~15ºC)
HEATING
The following parameters can be adjusted:
T4_heat_1 (0~5ºC)
T4_heat_2 (15~20ºC)
offset_h (0~15ºC)
T4
Tws'
Tws
of f set _c
T4_cool _1 T4_cool _2
T4
Tws'
Tws
of f set _h
T4_heat _1 T4_heat _2