- C O N T R O L -
47
menu: PARAMETERS – THERMOREG. – SET POINT
DEFAULT values
90 / CEN
SecondSetC
Secondary cooling Set Point
12
91 / CEN
SecondSetH
NOT USED - Secondary heating Set Point
35
118 / CEN
SetCool
Cooling Set Point
6.5
119 / CEN
SetHeat
NOT USED - Heating Set Point
45
272 / CEN
SetRecovery
NOT USED
35
menu: PARAMETERS – THERMOREG. – MAINTENANCE
114 / CEN
SetMantCool
Summer maintenance setpoint
15
117 / CEN
SetMantHeat
NOT USED - Winter maintenance setpoint
30
menu: PARAMETERS - THERMOREG.– ANTIFREEZE
115 / CEN
AllFreeze
Antifreeze alarm set
4
121 / CEN
PreAF
Antifreeze pre-alarm set
4.5
261 / CEN
SetResist
Antifreeze heater set
4
menu: PARAMETERS – SET – UNIT - EVAPORATORS
37 / EVAP
SetResist
Antifreeze heater set
4
39 / EVAP
ALLFreeze
Antifreeze alarm set
4
41 / EVAP
PreAF
Antifreeze pre-alarm set
4.5
KEYPAD USE
To enter in the SETUP
menu
?
ESC
I
HOME
button F3 SETUP
To select the submenu
?
ESC
I
HOME
buttons
▲▼
F2 – F3
To access
?
ESC
I
HOME
button F1 ENTER
To scrolling voices
?
ESC
I
HOM E
buttons
▲▼
F2 - F3
To go back a level of the
menu
?
ESC
I
HOME
button ESC
SET UP menu:
PARAMETERS
set point modification
SCHEDULING
enables/disables timing
bands
CLOCK SETUP
Set the clock
ID Tast-Cen
(ATC ONLY)
PASSWORD
(ATC ONLY)
To go back to the main
menu
?
ESC
I
HOME
button HOME