WDAT-3
2.160-3.660
- E L E C T R I C AL D AT A -
16
Acoustic configuration: extremely low noise (EN) / energy efficiency: high efficiency (H)
SIZES
2.160 2.180 2.200 2.220 2.250 2.280 2.300 2.320 2.340 2.360 2.390 2.420 2.450 2.480
COOLING
Cooling
capacity
1 kW 353 387 447.5 503.9 567.2 655.2 709.3 770.8 814.7 851.5 918.3 1007.7 1075.5 1105.4
Compressor power input
kW 123.1 135.5 156 180.6 195.3 223.1 250.6 274.8 292.3 308.1 305.7 327.3 367.4 382.1
Total
power
input
2 kW 133.4 145.8 168.7 193.3 208 238.2 265.7 289.9 308.6 325.6 330.7 352.3 392.4 407.1
EER
Nr 2.65 2.65 2.65 2.61 2.73 2.75 2.67 2.66 2.64 2.62 2.78 2.86 2.74 2.72
ESEER
Nr 3.98 3.98 3.98 3.91 4.1 4.12 4 3.99 3.96 3.93 4.16 4.29 4.12 4.07
COMPRESSOR
Type of compressors
3
DSW
No. of Compressors
Nr 2
Std Capacity control steps
Nr
stepless/6
Refrigerant circuits
Nr 2
INTERNAL EXCHANGER
Type of internal exchanger
4
S&T
No. of internal exchangers
Nr 1
Water flow-rate
l/s 16.9 18.5 21.4 24.1 27.1 31.3 33.9 36.8 38.9 40.7 43.9 48.1 51.4 52.8
Pressure drop
kPa
40 28 37 33 47 26 38 35 50 54 62 73 42 45
EXTERNAL EXCHANGER
Front surface
m
2
19 19 24 24 29.4
29.4 35 35 35 35 48 48 48 48
EXTERNAL SECTION FANS
Type of fans
5
AX
Number of fans
Nr 8 8 9 10 10 12 12 12 13 14 20 20 20 20
Standard air flow
l/s 26396 26396 31036 33270 35911 39919 50615 50615 53573 56531 66541 66541 66541
66541
CONNECTIONS
Water fittings
5"
6" / 8" 6" / 8"
6" / 8" 6" / 8"
8"
POWER SUPPLY
Standard power supply
V 400/3/50
STANDARD UNIT WEIGHTS
Shipping weight
kg 4835 4851 5683 6270 6525 6820 7820 8413 8700 8800 10814 11094 11284
11304
Operating weight
kg 4997 5013 5867 6492 6747 7072 8115 8796 9162 9262 11237 11517 11690
11710
(1) data referred to the following conditions :
internal exchanger water = 12/7°C
outside air temperature 35°C
(2) According to EUROVENT the Total Power Input does not consider the
pump share, required to overcome the pressure drop for the solution
circulation inside the exchangers.
(3) DSW = twin-screw compressor
(4) S&T = tube bundle
(5) AX = axial-flow fan
OPERATING LIMITS
SIZES
2.160 2.180 2.200 2.220 2.250 2.280 2.300 2.320 2.340 2.360 2.390 2.420 2.450 2.480
EXTERNAL EXCHANGER
Max air intake temperature
1 °C
44.5
43
44
41.5
42
41
39
39.5
39
39.5
40.5
42.5
41.5
41.5
Max
air
intake
temperature
2
°C
49 48 49 46 47 46 44 44 44 44 45 47 46 46
Min.
air
intake
temperature 3
°C -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10 -10
Min. air intake temperature
4
°C
-8 -9 -7 -9 -9 -9 -9 -9 -9 -9 -10 -9 -9 -9
Min. air intake temperature
5
°C
1 1 7 3 5 3 5 5 2 2 6 3 4 4
Min. air intake temperature
6
°C
12 13 17 14 15 13 15 15 14 14 16 14 14 14
INTERNAL EXCHANGER
Max water inlet temperature
7 °C
21
Min. water outlet temperature 8 °C
5
Min. water outlet temperature 9 °C
-8
Note: In any case, the unit should never be exposed to or operated,
transported and/or stored at temperatures below -10°C.
Note: the Standard unit shall never be exposed, at temperatures below -
10°C while supplied. On request it’s possible to take countermeasures for
the operation also in more critical environmental conditions. For special
conditions contact our Sales Office.
Note: the Standard unit shall never be exposed, at
temperatures below -10°C while supplied.
Warning: the still air condition is meant as absence of air flow to the unit.
Any wind condition can let air pass through the condenser coil thus
worsening the operating limits of the unit (see limits with air speed at 0,5 m/s
& 1 m/s). In order to avoid such situation, windbreak barriers are necessary.
The minimum ambient temperature is given for units equipped with low
ambient control or with ECObreeze fans. For standard unit without these
options, this value is of about 18°C with still air and unit operating at full
load.
(1) unit at full load
internal exchanger water = 12/7°C
(2) capacity-controlled unit (automatic capacity control)
(3) unit at full load
external exchanger air in quiet
(4) capacity-controlled unit (automatic capacity control)
external exchanger air in quiet
(5) capacity-controlled unit (automatic capacity control)
air to external exchanger = 0.5m/sec
(6) capacity-controlled unit (automatic capacity control)
external exchanger air = 1m/sec
(7) external exchanger air intake 35°C
(8) Standard Version
external exchanger air intake 35°C
(9) Low temperature version
external exchanger air intake 35°C
Fluid with ethylene glycol of 40%