WDAT-3
2.160-3.660
- E L E C T R I C AL D AT A -
17
Acoustic configuration: extremely low noise (EN) / energy efficiency: high efficiency (H)
SIZES
3.480 3.500 3.540
COOLING
Cooling
capacity
1
kW
1158 1208 1291
Compressor power input
kW 407.3
427
459.5
Total power input
2
kW
432.3
452
486.9
EER
Nr
2.68 2.67 2.65
ESEER
Nr 4.05
4.03
4
COMPRESSOR
Type of compressors
3
DSW
No. of Compressors
Nr 3
Std Capacity control steps
Nr
stepless/9
Refrigerant circuits
Nr 3
INTERNAL EXCHANGER
Type of internal exchanger
4
S&T
No. of internal exchangers
Nr 1
Water flow-rate
l/s
55.3 57.7 61.7
Pressure drop
kPa 51
63
71
EXTERNAL SECTION FANS
Type of fans
5
AX
Number of fans
Nr 20
20
22
CONNECTIONS
Water fittings
8"
POWER SUPPLY
Standard power supply
V 400/3/50
STANDARD UNIT WEIGHTS
Shipping weight
kg
13092 13337 13442
Operating weight
kg
13498 13812 13925
(1) data referred to the following conditions :
internal exchanger water = 12/7°C
outside air temperature 35°C
(2) According to EUROVENT the Total Power Input does not consider the
pump share, required to overcome the pressure drop for the solution
circulation inside the exchangers.
(3) DSW = twin-screw compressor
(4) S&T = tube bundle
(5) AX = axial-flow fan
OPERATING LIMITS
SIZES
3.480 3.500 3.540
EXTERNAL EXCHANGER
Max air intake temperature
1
°C
39
38
38
Max air intake temperature
2
°C
45
44
44
Min. air intake temperature
3
°C
-10
-10
-10
Min. air intake temperature
4
°C
-9 -9 -9
Min. air intake temperature
5
°C 1
1
1
Min. air intake temperature
6
°C 13
13
13
INTERNAL EXCHANGER
Max water inlet temperature
7
°C
21
Min. water outlet temperature
8
°C
5
Min. water outlet temperature
9
°C
-8
Note: the Standard unit shall never be exposed, at temperatures below -
10°C while supplied. On request it’s possible to take countermeasures for
the operation also in more critical environmental conditions. For special
conditions contact our Sales Office.
Warning: the still air condition is meant as absence of air flow to the unit.
Any wind condition can let air pass through the condenser coil thus
worsening the operating limits of the unit (see limits with air speed at 0,5 m/s
& 1 m/s). In order to avoid such situation, windbreak barriers are necessary.
The minimum ambient temperature is given for units equipped with low
ambient control or with ECObreeze fans. For standard unit without these
options, this value is of about 18°C with still air and unit operating at full
load.
(1) unit at full load
(2) capacity-controlled unit (automatic capacity control)
(3) unit at full load
external exchanger air intake 35°C
(4) capacity-controlled unit (automatic capacity control)
external exchanger air in quiet
(5) capacity-controlled unit (automatic capacity control)
air to external exchanger = 0.5m/sec
(6) capacity-controlled unit (automatic capacity control)
external exchanger air = 1m/sec
(7) external exchanger air intake 35°C
(8) Standard Version
external exchanger air intake 35°C
(9) Low temperature version
external exchanger air intake 35°C
Fluid with ethylene glycol of 40%