8 MAINTENANCE
Safety valve
The pressure relief valve must be replaced :
if it has intervened
if there is oxidation
based on the date of manufacture, in compliance with local
regulations.
Valve replacing
The 3-piece joint allows the valve replacement.
turn off the shut-off valve
remove the safety valve
DO NOT WARM THE PIECE
remove the valve from the joint
assemble the new valve to the joint
clean the parts to be assembled and apply white paste
install the new valve
turn on the shut-off valve
A saftey
valve
B white
paste
C joint 3 pieces
D shut-off valve