3 SELECTING THE INSTALLATION SITE
Positioning
Installation must be in accordance with local regulations. If
they do not exist, follow EN378
.
During positioning consider these elements:
customer approval
unit weight and bearing point capacity
safe accessible position
functional spaces
spaces for the air intake/exhaust
electrical connections
max. distance allowed by the electrical connections
water connections
Functional spaces
Functional spaces are designed to:
guarantee good unit operation
carry out maintenance operations
protect authorized operators and exposed people
Respect all functional spaces indicated in the TECHNICAL
INFORMATION section.
Positioning
Units are designed to be installed:
EXTERNAL
in fixed positions
Put the unit in a position where any leaking gas cannot enter
buildings or stagnate in closed areas. In the latter case,
observe the rules for machinery rooms (ventilation, leak
detection, etc.).
Installation standards:
install the unit raised from the ground
bearing points aligned and leveled
discharged condensation water must not cause harm/danger
to people and property
the accumulation of snow must not cause clogging of the
coils
avoid installations in places subject to flooding
Limit vibration transmission:
use anti-vibration devices or neoprene strips on the unit
support points
install flexible joints on the hydraulic connections
Protect the unit with suitable fence in order to avoid access to
unauthorised personnel (children, vandals, etc.)
A correct circulation of the air is mandatory to guarantee the
good unit operating..
The unit must be level.
Summary of Contents for R513A
Page 1: ...R513A MANUAL FOR INSTALLATION USE AND MAINTENANCE WDAT ik4 120 1 580 2 MF500002 00 11 20...
Page 20: ...20 5 ELECTRICAL CONNECTIONS...
Page 34: ...34 7 CONTROL...
Page 35: ...35 7 CONTROL...
Page 36: ...36 7 CONTROL...
Page 37: ...37 7 CONTROL...
Page 52: ...52 9 ANTIVIBRATION MOUNTS...
Page 53: ...53 9 ANTIVIBRATION MOUNTS...
Page 73: ......