Water side heat exchanger
The exchanger must to be able to provide the maximum thermal
exchange, therefore it is essential for the inner surfaces to be
clean of dirt and build-up.
Periodically check the difference between the temperature of the
supply water and the condensation temperature: if the difference
is greater than 8°C–10°C it is advisable to clean the exchanger.
The clearing must be effected:
with circulation opposite to the usual one
with a speed at least 1,5 times higher than the nominal one
with an appropriate product moderately acid (95% water +
5% phosphoric acid)
after the cleaning rinse with water to inhibit the action of any
residual product
Water filter
Check that no impurities prevent the correct passage of water.
Flow switch
controls the operations
remove incrustations from the palette
Circulation pumps
Check:
no leaks
Bearing status (anomalies are highlighted by abnormal noise
and vibration)
The closing of terminal covers and the correct positioning of
the cable glands.
Insulations
Check the condition of the insulations: if necessary, apply glue
and renew the seals.