23
Modbus - RS485
Option
LED BSP
communication with AP1 module
LED BUS
communication with Modbus
green
communication ok
green
communication ok
yellow
software ok but communication with AP1 down
yellow
startup / channel not communicating
red
flashing: software error
fixed: hardware error
red
communication down
Modbus / LonWorks / Cable requirements
Couple of conductors twisted and shielded Section of conductor
0,22mm2…0,35mm2 Rated power between conductors < 50 pF/m
Nominal impedance 120
Ω
Recommended cable BELDEN 3106A
very RS485 serial line must be set up using the ‘In/Out’ bus
system.
Other types of networks are not allowed, such as Star or Ring
networks.
The difference in potential between the earth of the two RS485
devices that the cable shielding needs to be connected to must
be lower than 7 V
There must be suitable arresters to protect the serial lines from
the effects of atmospheric discharges
A 120 ohm resistance must be located on the end of the serial
line. Alternatively, when the last serial board is equipped with
an internal terminator, it must be enabled using the specific
jumper, dip switch or link.
The cable must have insulation features and non-flame
propagation in accordance with applicable regulations.
The RS485 serial line must be kept as far away as possible
from sources of electromagnetic interference.
A. Unit
B. Metal conduit
C. Metal septums
D. Metal-lined sheath (sleeve)
5 ELECTRICAL CONNECTIONS
Summary of Contents for R513A
Page 1: ...R513A MANUAL FOR INSTALLATION USE AND MAINTENANCE WDAT ik4 120 1 580 2 MF500002 00 11 20...
Page 20: ...20 5 ELECTRICAL CONNECTIONS...
Page 34: ...34 7 CONTROL...
Page 35: ...35 7 CONTROL...
Page 36: ...36 7 CONTROL...
Page 37: ...37 7 CONTROL...
Page 52: ...52 9 ANTIVIBRATION MOUNTS...
Page 53: ...53 9 ANTIVIBRATION MOUNTS...
Page 73: ......