Table 3: Antifreeze Percentages by Volume
Table 2: Approximate Fluid Volume (U.S. gal. [L]) per
100' of Pipe
Ground-Loop Heat Pump Applications
Air Pad or
Extruded
polystyrene
insulation board
P/T Plugs
Insulated
Hose Kit
Flow
Controller
To Loop
Unit Power
Disconnect
AH & Thermostat
Wiring
Figure 7: Loop Connection (Indoor
Compressor Section)
Type
Minimum Temperature for Low Temperature Protection
10°F [-12.2°C]
15°F [-9.4°C]
20°F [-6.7°C]
25°F [-3.9°C]
Methanol
100% USP food grade Propylene Glycol
Ethanol*
25%
38%
29%
21%
25%
25%
16%
22%
20%
10%
15%
14%
* Must not be denatured with any petroleum based product
Fluid Volume (gal [liters] per 100’ [30 meters) Pipe)
Pipe
Size
Volume (gal) [liters]
Copper
1”
4.1 [15.3]
1.25”
6.4 [23.8]
2.5”
9.2 [34.3]
Rubber Hose
1”
3.9 [14.6]
Polyethylene
3/4” IPS SDR11
2.8 [10.4]
1” iPS SDR11
4.5 [16.7]
1.25” IPS SDR11
8.0 [29.8]
1.5” IPS SDR11
10.9 [40.7]
2” IPS SDR11
18.0 [67.0]
1.25” IPS SCH40
8.3 [30.9]
1.5” IPS SCH40
10.9 [40.7]
2” IPS SCH40
17.0 [63.4]
Unit Heat Exchanger
Typical
1.0 [3.8]
Flush Cart Tank
10” Dia x 3ft tall
[254mm x 91.4cm tall]
10 [37.9]
R e s i d e n t i a l S p l i t U n i t s - 6 0 H z P u r o n
®
R e v. : 6 D e c . , 2 0 1 1
14